I. Brief
1.1 Name and Model: 12kV pad mounted metering unit PMY5-12, combined transformer JLSZXW5-12
1.2 Description
This metering unit is for outdoor installation, in power distribution system upto 12kV(Um) for metering and measuring, with a factory-assembled three-phase combined transformer of CT, VT inside. Three-phase voltage transformers’ wiring method Y-Y star connection, and current transformer is optional, eg. two-phase CT, three-phase CT. Panel type is metal-clad, made from galvanized steel, stainless steel, or alloy aluminum. Enclosure surface is painted with color and protection layer for resistance to acid and alkali corrosion, and UV radiation. It is applied to connecting outdoor underground cable with utility company power system. The metering unit has two compartments, including a factory-assembled low voltage compartment for energy meter, and test terminal block of combined transformers. End customers can install a suitable energy meter in the compartment.
1.3 Electrical data
No. | item | units | specification |
| Highest voltage for
| kV | 12 |
| rated frequency | Hz | 50, 60 or 50/60 |
| Rated lightning impulse
| kV | 75 kV, 95 kV |
| Rated power-frequency
| kV | 28 |
| Rated power-frequency
| kV | 3 |
| Number of CTs and VTs | pcs | 3VT+3CT or 2CT+3VT |
| Standard | / | IEC 61869-1:2007 | IEC 61869-2:2012 IEC 61869-3:2011 | IEC 61869-4:2013 |
No | Item | specification |
| Rated primary current | 5A up to 600A |
| Rated secondary current | 5A, 1A |
| Rated Continuous Thermal Current | 120%, 125%, 150%, 200% etc. |
| Rated Short time current (Ith) (thermal 1 second) | 80xIpr, 100xIpr |
| Rated Dynamic Current (Idyn) | 2.5xIth |
| Rated Output(VA) | 12.5, 15,20 |
| Accuracy Class | 0.2S, 0.2, 0.5S, 0.5, 1 metering |
| Instrument Security Factor (FS) | 5, 10 |
| Applicable Standard | IEC: 61869-1&2 |
No | Item | specification |
| Rated primary voltage(V) | 10000/√3, 11000/√3 |
| Rated secondary voltage(V) | 100/√3, 110/√3 |
| Rated Voltage Factor | 1.2/Continuous 1.5/30s, 1.9/30s, 1.9/8h |
| Standard connection | Y-Y (star connection) |
| Rated Output(VA) | 15, 20, 25, 30, 50, 75 |
| Accuracy Class | 0.2, 0.5, 1, 3 metering |
| Thermal burden(VA) | 300, 400 |
| Applicable Standard | IEC: 61869-1&3 |
Other specifications are available as per clients’ requests
V. Dimensional drawing and wiring
dimensional drawing
wiring
VI. Special requirements
Other specifications are available as per clients’ requests.