Specifications
Brand Name :
Chuangyin
Model Number :
JLSZVW-12(OMV-12)
Place of Origin :
China
Delivery Time :
25-35 working days
Packaging Details :
Wooden frame and stretch film
Highest voltage for equipment Um (r.m.s.) :
12KV
Rated frequency :
50, 60 or 50/60HZ
Standard :
IEC 61869-1:2007, IEC 61869-2:2012 IEC 61869-3:2011,IEC 61869-4:2013
Rated primary current :
5A up to 1000A
Rated secondary voltage(V) :
100,110,115,120
Thermal burden(VA) :
300
Description

1. Product introduction:

1.1 Product type name and model: Install the metering box OMV-12, JLSZVW-12 type combined transformer on the 12kV medium voltage overhead column

1.2 Product overview:

This type of metering box is an outdoor dry three-phase primary metering unit. The medium-voltage metering combination transformer is epoxy resin cast and solid-sealed. It consists of two current transformers and two voltage transformers to form three-phase VV wiring, medium voltage The metering combination transformer is vacuum cast with cycloaliphatic epoxy resin (CEP). It has excellent insulation properties and hydrophobicity. The surface is resistant to acid and alkali corrosion, contamination, and UV. It is suitable for outdoor overhead line installation and connection to public power systems. The metering box can be equipped with a metering meter box. All the secondary leads of the transformer can be connected and collected in the meter box. It is also equipped with a test terminal block and a meter installation space. The meter can be configured according to the requirements or the user can configure the meter. Just plug in, and it is suitable for electrical energy metering, current and voltage measurement in urban and rural power distribution network lines with a maximum voltage of 12kV and below.

1.3 Basic parameters:

No.

Item

Units

Specification

Highest voltage for
equipment Um (r.m.s.)

kV

12

rated frequency (fR)

Hz

50, 60 or 50/60

Rated lightning impulse
withstand voltage (peak)

kV

75 kV,95 kV

Rated power-frequency
withstand voltage on primary

kV

28

Rated power-frequency
withstand voltage on secondary

kV

3

Number of CTs and VTs

pcs

2VT+2CT

Standard

/

IEC 61869-1:2007, IEC 61869-2:2012 IEC 61869-3:2011,IEC 61869-4:2013

2. Product function and use:
Overhead pole mounted primary metering unit Comply with the latest applicable industry standards and local and/or national electrical regulations. It is used for three-phase overhead power grid energy measurement management and distribution network automation management system. The primary side measurement is more accurate, and the power loss of the line can be effectively measured to reduce losses.

3. Main features of the product:
1. The integrated solid package of the medium voltage combined transformer of the metering unit has a compact and beautiful design, eliminating the need for multiple single transformer combined installation and ring connection, and can be installed directly on the pole outdoors, which is convenient and quick;
2. The metering unit can be equipped with a meter box as required and connected to the transformer connection. The meter is installed in the box, and the meter box door switch sensor alarm signal is reserved. The door lock seal structure is designed to prevent electricity theft;
3. The meter box body is made of corrosion-resistant stainless steel or low-carbon steel of the same performance, and the sealing design is weather-proof, and the surface is coated with an anti-corrosion paint powder layer, which is resistant to acid and alkali corrosion and UV;
4. The medium voltage combination transformer is insulated with epoxy resin solid encapsulation, and the surface is dirt-resistant, UV resistant, and has excellent dielectric and mechanical properties. Compared with the dispersed single-phase combination transformer, its size is more compact, oil-free, gas-free Maintenance to meet the requirements of safe operation and environmental protection;
5. The CT of the medium voltage combined transformer can be configured with double transformation ratios, and it is convenient to set the changeover switch. The VT is equipped with anti-short circuit and overload protection design to avoid burning and explosion caused by VT short circuit and overload.
6. The primary connection adopts the contact bar and the terminal clamp connection. The terminal block of the corresponding area can be configured according to the user's requirements, the lightning arrester mounting bracket is reserved, and the lightning arrester can be configured at the primary end as required.

4. Product technical parameters:
Current transformer specifications

No

Item

Specification

Rated primary current

5A up to 1000A

Rated secondary current

5A或1A

Rated Continuous Thermal Current

120%,125%,150%,etc.

Rated Short time current (Ith) (thermal 1 second)

80xIpr,100xIpr

Rated Dynamic Current (Idyn)

2.5xIth

Rated Output(VA)

5,10,12.5,15,20

Accuracy Class

0.2S,0.2,0.5S,0.5,1 Metering

Instrument Security Factor (FS)

5,10

Applicable Standard

IEC: 61869-1&2

Voltage transformer specifications

No

Item

Specification

Rated primary voltage(V)

10000,11000

Rated secondary voltage(V)

100,110,115,120

Rated Voltage Factor

1.2/Continuous

1.5/30s

Standard connection

V-V connection

Rated Output(VA)

15,20,25,30,50,75

Accuracy Class

0.2,0.5,1,3 Metering

Thermal burden(VA)

300

Applicable Standard

IEC: 61869-1&3

If the parameters required by the user exceed the range of the above table, it can be determined after consultation with our company.

5. Product dimensions and wiring schematic diagram:

Overhead Pole Mounted 12kV 1000A Primary Metering Unit 2CT

Overhead Pole Mounted 12kV 1000A Primary Metering Unit 2CT

Overhead Pole Mounted 12kV 1000A Primary Metering Unit 2CT

Wiring schematic diagram

6,special instructions
The company can design and manufacture specially according to the special requirements of customers.

Send your message to this supplier
Send Now

Overhead Pole Mounted 12kV 1000A Primary Metering Unit 2CT

Ask Latest Price
Brand Name :
Chuangyin
Model Number :
JLSZVW-12(OMV-12)
Place of Origin :
China
Delivery Time :
25-35 working days
Packaging Details :
Wooden frame and stretch film
Highest voltage for equipment Um (r.m.s.) :
12KV
Contact Supplier
Overhead Pole Mounted 12kV 1000A Primary Metering Unit 2CT

Shenzhen Chuangyin Co., Ltd.

Verified Supplier
7 Years
guangdong, shenzhen
Since 2002
Business Type :
Manufacturer, Exporter
Total Annual :
9210000-15350000
Employee Number :
500~999
Certification Level :
Verified Supplier
Contact Supplier
Submit Requirement