Summarize
Multifunctional power meter can measure the power parameters used in three-phase power system with high precision: three-phase voltage, current, active power, reactive power, power factor, grid frequency, active power, reactive power, and with communication interface and power pulse output function. MODBUS-RTU communication protocol is used to realize LED field display and remote RS-485 digital communication. It has the characteristics of easy connection and installation, simple wiring, convenient maintenance, small engineering amount, field programmable setting input parameters, etc., and can complete the networking communication with different PLC and industrial control computers in the industry.
Peculiarity
Measurement: three-phase voltage, current, active power, reactive power, power factor, frequency, active power, reactive power
Display: three rows of LED digital tube display, high visibility
Communication: RS485 communication, MODBUS-RTU communication protocol
Output: two power pulse output (pulse constant 3200imp/kwh)
Expansion: can directly input signal from current, voltage, transformer, field programmable setting of input parameter ratio Use: incoming line, bus and important distribution loop, using GCS, GCK, MNS, GGD and other cabinet types
Product model and size
Model number | CQ42-3E | CQ96-3E | CQ80-3E | CQ72-3E |
Face frame size | 120*120 | 96*96 | 80*80 | 72*72 |
Opening size | 111*111 | 91*91 | 76*76 | 67*67 |
Technical index
Argument | |||
Accuracy level | Power metering: Active power 0.5, reactive power 1.0, converter output 0.5 | ||
Display mode | LCD display / 12-bit LED display | ||
The signal is entered | Measurement network | Three-phase four-wire V34/ three-phase three-wire V33 | |
Voltage | Rated value | AC380V/AC100V | |
Overload | Duration: 1.2 times instantaneous: 2 times (10 seconds) | ||
Power dissipation | <1VA(per phase) | ||
Impedance | >300kΩ | ||
Electric current | Rated value | AC5A/AC1A | |
Over duty | Duration: 1.2 times instantaneous: 2 times (10 seconds) | ||
Power dissipation | <0.4VA(per phase) | ||
Impedance | < 2 m Ω | ||
Frequency | 45-65Hz | ||
Harmonic wave | Voltage and current total harmonic content and 3-15 odd harmonic components | ||
Electric energy | Bidirectional active and reactive energy metering | ||
Power source | Scope of work | AC/DC85~264V | |
Power dissipation | <5VA | ||
Work and energy modules | Electrical energy pulse | Passive optocoupler output | |
Communication interface | Two RS485 communication ports, Modbus-RTU communication protocol | ||
Communication baud rate: 4800-9600, no parity check N81, E81, or 081 | |||
The second RS485 communication port can be configured as PROFIBUS-DP | |||
Switching input | Passive dry junction input | ||
Switching output | Over limit alarm or remote relay output capacity AC5A/250V,DC5A/30V | ||
Converter output | 0~20mA/4~20mA/0~5V/1~5V converter output, programmable setting of converter items and corresponding output values | ||
Working environment | Ambient temperature: -10~55℃, relative humidity <93%, no corrosive gas place, altitude <2500M | ||
Storage environment | -20~75℃, relative humidity ≤93% | ||
Clock error | < 0.5 s/d | ||
Secure | Insulation | The resistance of signal, power and output terminals to the shell is >100MΩ | |
Withstand voltage | Input voltage >2kV, input and output >1kV, power supply and output >2kV |