Item | Parameters | Remark |
Model | LI-48125AH | 15S6P |
Rated Voltage(V) | 48 | LFP27070150-3.2V21AH |
Typical Capacity(Ah) | 125 | 25℃ 0.5C discharge |
Standard Charge Voltage(V) | 54.75 | Can be set |
Float Charge Voltage(V) | 51.0~51.75 | Can be set |
Maximum Charge Current(A) | 100 | |
Maximum Discharge Current(A) | 125 | |
Over-charge protection voltage (V) | 54.75 | Can be set |
Over-discharge protection voltage (V) | 40.5 | Can be set |
Over-charge protection voltage of single cell(V) | 3.65 | Can be set |
Over-discharge protection voltage of single cell (V) | 2.7 | Can be set |
Over-discharge protection current (A) | 150 | Can be set |
Maximum Temperature Protect at Charge(℃) | 55 | Can be set |
Minimum Temperature Protect at Charge (℃) | 0 | Can be set |
Maximum Temperature Protect at Discharge (℃) | 65 | Can be set |
Minimum Temperature Protect at Discharge (℃) | -20 | Can be set |
BMS leakage current(mA) | ≤1 | |
Maximum Balanced Current(mA) | 200 | |
Dimensions(mm) | 482(width)*178(height)*680(length) | |
Weight(kg) | 105 | Net weight |
Cycle Life
Item | Test method | Criteria |
Cycle life |
1) The ambient temperature for test is 25 ± 5°C. 2) The pack is charged with standard charging method 3) After rest for 30 min at open circuit state, pack is discharged with 0.2C A to cut-off voltage; then rest for 30 min. 4) Repeat above steps till both of the two continuous cycles discharge capacity are less than 80% nominal capacity; then record the cycle numbers. |
Cycle life ≥ 1500 cycles |