Rechargeable AGM UPS 12v 100ah Deep Cycle Battery For Solar Power Home System
Introduction of 12v 100ah Deep Cycle Battery
Specification of 12v 100ah Deep Cycle Battery
Battery Type | VRLA Battery |
Nominal Voltage | 12V |
Number of cell | 6 cells |
Nominal Capacity | 100Ah (10hr, 1.80V/ c e l l , 25°C) |
Approx Weight (kg) | 35 Kg |
Designed Life(Float Charge 20°C) |
12 Years |
Short Circuit Current | 1900 A |
Operation Ambient Temperature |
-20°C ~ 55°C |
Optimal Ambient Temperature |
20°C ~ 25°C |
Internal resistance | 6.3 mΩ |
Self-discharge | max 3% per month @20°C |
Depth of Discharge |
30% : 1200 50%: 500 100%: 300 |
Max discharge current | 900A (5s) |
Container Material | ABS |
Terminal (mm) | M6 female, front access terminal |
Constant Currant Discharge Ratings-amperes at 25°C
F.V/Time | 15min | 30min | 1h | 2h | 3h | 4h | 5h | 6h | 8h | 10h | 20h |
1.60V | 190 | 113 | 68.6 | 42.3 | 30.1 | 23.7 | 19.4 | 16.7 | 12.8 | 10.7 | 5.5 |
1.65V | 186 | 112 | 67.9 | 42.0 | 29.9 | 23.6 | 19.3 | 16.6 | 12.8 | 10.7 | 5.5 |
1.70V | 179 | 109 | 66.8 | 41.4 | 29.5 | 23.3 | 19.1 | 16.4 | 12.7 | 10.6 | 5.5 |
1.75V | 169 | 105 | 65.1 | 40.4 | 28.9 | 22.9 | 18.9 | 16.2 | 12.6 | 10.5 | 5.4 |
1.80V | 153 | 99.3 | 62.5 | 38.8 | 28.0 | 22.1 | 18.5 | 15.9 | 12.4 | 10.3 | 5.3 |
1.85V | 129 | 91.5 | 58.8 | 36.5 | 26.5 | 21.3 | 17.8 | 15.4 | 12.0 | 10.0 | 5.2 |
Constant Power Discharge Ratings-watts at 25°C
F.V/Time | 15min | 30min | 1h | 2h | 3h | 4h | 5h | 6h | 8h | 10h | 20h |
1.60V | 285 | 202 | 127 | 78.2 | 57.5 | 45.7 | 38 | 32.5 | 25.1 | 20.6 | 10.8 |
1.65V | 282 | 201 | 126 | 77.7 | 57.2 | 45.5 | 37.7 | 32.4 | 25 | 20.6 | 10.8 |
1.70V | 276 | 199 | 125 | 76.9 | 56.5 | 45.1 | 37.5 | 32.1 | 24.8 | 20.4 | 10.8 |
1.75V | 267 | 195 | 123 | 75.6 | 55.5 | 44.4 | 37 | 31.8 | 24.6 | 20.2 | 10.7 |
1.80V | 254 | 188 | 120 | 73.7 | 54.1 | 43.4 | 36.2 | 31.2 | 24.2 | 19.9 | 10.5 |
1.85V | 235 | 178 | 115 | 70.8 | 52.0 | 41.8 | 35 | 30.3 | 23.6 | 19.5 | 10.3 |
Application Fields of 12v 100ah Deep Cycle Battery
1. Telecommunications
2. SPC Exchange
3. UPS System
4. Marine Equipment
5. Power Station, Switching System, DC power system
Advantages
1. Long Life: 12 years design life in floating condition
2. Wide operating temperature range: from -15°C to 60℃
3. Advanced paste formula with increased recharge efficiency
4. Front access terminal with standard width for 19” and 23” ETSI racks
5. 30% decreased float current lead to excellent high temperature resistance