Model | HV500 Low Voltage Engineering Single-Drive Inverter |
iInput/output Power | Input Uin | 200V (-15%) ~240V (+10%) 3Phase , 380V (-15%) ~480V (+10%) 3Phase, |
500V (-15%) ~690V (+10%) 3Phase |
Input Frequency | 50Hz/60Hz±5% |
Unbalance Degree of Uin | ≤3% |
Output Uout | 0V~Input Uin |
Output Frequency | 0Hz~500Hz |
Power range | 2.2kW~560kW |
Control Performance | Motor Type | Asynchronous / Synchronous |
Control Method | V/F, OLVC (Open-Loop Vector Control), CLVC (Close-Loop Vector Control) |
Range of Speed Regulation | 1:10 V/F, 1:100 OLVC, 1:1000 CLVC |
Start Torque | VF: 100% (0.5Hz), OLVC: 150% (0.5Hz), CLVC: 180% (0Hz) |
Torque Precision | ≤5%, Vector Control |
Torque Pulsation | ≤5%, Vector Control |
Speed Regulation Precision | OLVC 0.2%, CLVC 0.01% |
Torque Response | <5ms, Vector Control |
Dynamic Speed Reduction | OLVC<0.5%*s, CLVC<0.3%*s |
Acceleration and Deceleration Time | 0.0s~3200.0s, 0.0min~3200.0min |
Torque Lifting | 0.0%~30.0% |
Overload | Heavy Load Application 150% 1min/5min, Light Load Application 110% 1min/5min |
V/F Curve | Multiple ways: linear V/F curve, 5 kinds of torque reduction characteristic curve mode (2.0 power, 1.8 power, 1.6 power, 1.4 power, 1.2 power), user-defined VF curve |
Input Frequency Accuracy | Digital: 0.01Hz, Analog: 0.01Hz |
Control Performance | Acceleration and Deceleration Curve | Straight, S Curve |
Multiple Speed-Steps Operation | 16-Speed Steps Operation through control terminals |
Automatic VoltageAdjustment (AVR) | Keeping the output voltage constant automatically when the grid voltage changes within a certain range |
Fixed Length | Setted and Fixed Length Control |
In-build PID | It Can Easily Constructed Closed loop control system |
Enhencement Function | Free Function Block |
iInput/output | Set Frequency | Keyboaed, UP/DOWN Terminals, Multiple Speed-Steps Operation, Terminals Pulsation, Com |
Power |
Analog Input Terminals | AI1: 0V~10V/-10V~10V, AI2: 0V~10V/0(4) mA~20mA |
Digital Input Terminals | DI1-DI6, 6 programmable digital input terminals, optocoupler isolation, compatible with drain/source input |
Digital Input/Output Terminals | DIO1: Fast pulse output, normal input/output; DIO2: fast pulse input, normal input/output |
Anolog Output Terminals | 2 Strings 0V~10V/0 (4) mA~20mA |
Relay Output | 2Strings Contact Type FormC |
Motor Temperature Detection | Support PT100/PT1000/KTY84 |
STO Interface | SIL3/PLe Safe torque shutdown function |
Com | Com Protocol | Modbus RTU (Standard), Profibus,CANopen,profinet,Devicenet,ControlNet |
profinet,Devicenet,ControlNet |
t |
Environment | Altitude | Without Derating Operation Within 2000m Altitude; 2000m~4000m, Each 100m lifting, Derating 1% (Current) |
Operation Temperature | -25℃~+40℃ (40℃~55℃ Derating) |
Humidity | 15%~95%, Without Condensation |
Vibration | 3M3, IEC60721-3-3 |
Storage Temperature | -40℃~+70℃ |
Operation Place | Indoor, Without direct sunlight, no flammable, corrosive gases, liquids and conductive particles |
Accessory | Encoding card, communication expansion card, voltage detection card |
Protection Function | Short circuit, over current, overload, over voltage, under voltage, phase loss, over temperature, external fault, etc. |
Efficiency | 5.5kW~22kW: ≥93%; Above 30kW: ≥95% |
Installation Method | Cabinet |
Protection Degree | IP20 |
Cooling | Forced Air Cooling |