Technical characteristics
220V single phase input VFD frequency converter 0.75kw 1hp For Air Compressor
Power class and catalog
Single-phase 220v±15% 0.75-2.2kw
Three-phase 380V±15% 0.75-315kw
Series of VFD | Outer size (H*W*T) (mm) | VFD Model | Adaptive motor (KW)
| Rated output current (A) |
FPR500M | Three phases motor power: 380-460V 50/60Hz | |||
170*85*140 | FPR500M-0.75G-T4 | 0.75 | 2.3 | |
FPR500M-1.5G-T4 | 1.5 | 3.8 | ||
FPR500M-2.2G-T4 | 2.2 | 5 | ||
185*118*157 | FPR500M-4.0G-T4 | 4 | 9 | |
248*160*178 | FPR500M-11G-T4 | 11 | 25 | |
320*220*197 | FPR500M-22G-T4 | 22 | 45 | |
FPR500A Single phase | Single phase motor power: 220-240V 50/60Hz | |||
185*118*157 | FPR500A-0.75G-S2 | 0.75 | 4.5 | |
FPR500A-1.5G-S2 | 1.5 | 7 | ||
FPR500A-2.2G-S2 | 2.2 | 11 | ||
FPR500A Three phases | Three phases motor power: 380-460V 50/60Hz | |||
185*118*157 | FPR500A-0.75G-T4 | 0.75 | 2.3 | |
FPR500A-1.5G-T4 | 1.5 | 3.8 | ||
FPR500A-2.2G-T4 | 2.2 | 5 | ||
248*160*178 | FPR500A-4.0G/5.5P-T4 | 4/5.5 | 9/13 | |
FPR500A-5.5/7.5PG-T4 | 5.5/7.5 | 13/17 | ||
FPR500A-7.5G/11P-T4 | 7.5/11 | 17/25 | ||
320*220*197 | FPR500A-11G/15P-T4 | 11/15 | 25/32 | |
FPR500A-15G/18.5P-T4 | 15/18.5 | 32/37 | ||
FPR500A-18.5G/22P-T4 | 18.5/22 | 37/45 | ||
460*285*234 | FPR500A-22G/30P-T4 | 22/30 | 45/60 | |
FPR500A-30G/37G-T4 | 30/37 | 60/75 | ||
FPR500A-37G/45P-T4 | 37/45 | 75/91 | ||
550*320*303 | FPR500A-45G/55P-T4 | 45/55 | 91/112 | |
FPR500A-55G/75P-T4 | 55/75 | 112/150 | ||
650*375*345 | FPR500A-75G/90P-T4 | 75/90 | 150/176 | |
FPR500A-90G/110P-T4 | 90/110 | 176/210 | ||
FPR500A-110G/132P-T4 | 110/132 | 210/253 | ||
765*500*350 | FPR500A-132G/160P-T4 | 132/160 | 253/304 | |
FPR500A-160G/185P-T4 | 160/185 | 304/330 | ||
FPR500A-185G/200P-T4 | 185/200 | 330/377 | ||
FPR500A-200G/220P-T4 | 200/220 | 377/426 | ||
1300*750*465 | FPR500A-220G/250P-T4 | 220/250 | 426/465 | |
FPR500A-250G/280P-T4 | 250/280 | 465/520 | ||
FPR500A-280G/315P-T4 | 280/315 | 520/585 | ||
FPR500A-315G/355P-T4 | 315/355 | 585/650 | ||
-FPR500E is for Synchronous permanent magnet motor, price is as same as FPR500A.
| ||||
-Warranty time: 18months
| ||||
-Price will be adjusted with the fluctuation of exchange rate. |
Technical characteristics
Item | Specifications | |
Basic function | Over load capability | G type:150% rated current 60s;180% rated current 3s |
P type:120% rated current 60s;150% rated current 3s | ||
Torque boost | Auto torque boost function; Manual torque boost 0.1%~30.0% | |
V/F curve | Linear V/F, multi-point V/F and square V/F curve(power of 1.2,1.4,1.6,1.8,2) | |
V/F separation | 2 ways: separation and semi-separation | |
Acc./dec curve | Straight line or S curve acceleration and deceleration mode, | |
Four kinds of acceleration and deceleration time. Acceleration and deceleration time range from 0.0s to 6500.0s | ||
DC braking | DC braking frequency:0.00Hz to maximum frequency. Braking time:0.0s to 36.0s | |
Brake current value:0%-100% | ||
Jog control | Jog frequency range:0.00Hz~50.00Hz; | |
Jog acceleration/deceleration:0.0s~6500.0s. | ||
Simple PLC | It can realize at maximum of 16 segments speed | |
Basic function | Multiple segment speed running | Running via the built-in PLC or control terminal. |
Built-in PID | It is easy to realize process-controlled closed loop control system. | |
Auto voltage regulation (AVR) | It can keep constant output voltage automatically in the case of change of network voltage. | |
Over-voltage/current stall control | It can limit the running voltage/current automatically and prevent frequent over-voltage/current tripping during the running process. | |
Quick current limit | Minimize the over-current fault, protect normal operation of the AC Drive. | |
Torque limit & control | "Excavators" characteristics, automatically limit torque during operation, prevent frequent over-current tripping. Closed loop vector mode can realize the torque control. | |
Personalized function | Instantaneous stop non-stop | When instantaneous power off, voltage reduction is compensated through load feedback energy, which could make AC Drive keep running in a short period of time. |
Rapid current limit | To avoid AC Drive frequent over-current fault. | |
Timing control | Timing control function:set time range 0Min~6500.0Min. | |
Running | Command source | Operation panel reference, control terminal reference and serial communication port reference. These channels can be switched in various modes. |
Frequency source | There are totally eleven types of frequency sources, such as digital reference, analog voltage reference , analog current reference, pulse reference, MS speed, PLC, PID and serial port reference. | |
Input terminal | 3 digital input terminals. | |
1 analog input terminals. | ||
1 supporting 0-10V voltage input or 0~20mA current input terminal. | ||
Output terminal | ||
1 relay output terminals. | ||
Keyboard operation | Keyboard potentiometer | Equipped with keyboard potentiometer or coding potentiometer. |
Keyboard operation | Protection function | It can implement power-on motor short-circuit detection, input /output phase loss protection, over current protection, over voltage protection, under voltage protection, overheating protection and overload protection.
|
Environment | Using place | Indoor, and be free from direct sunlight, dust, corrosive gas, combustible gas, oil smoke, vapor, drip or salt. |
Altitude | Below 1000m | |
Ambient temperature | -10 ℃ to +40 ℃ (Derating use when under ambient temperature of 40 ℃ to 50 ℃) | |
Humidity | Less than 95%RH,without condensing | |
Vibration | Less than 5.9m/s (0.6g) |
Company Profile