Introduction:
- This GIS Hipot Testing Equipment is mainly used for ac withstand voltage test of cross-linked cable, hydraulic generator, main transformer, bus, GIS, etc.
- It has a wide range of application and is an ideal withstand voltage equipment for local, municipal and count-level high voltage test departments and electric power installation and repair and test engineering units.
- It is mainly composed of frequency conversion control power supply, excitation transformer, reactor, capacitor voltage divider and compensation capacitor (optional).
Functions:
- This Hipot Testing Equipment has protection functions such as overvoltage, overcurrent, zero start, system detuning (flashover), overvoltage and overcurrent protection values can be set according to user needs, and flashover protection action when the sample flashes to protect the product.
- The entire unit is lightweight and easy to use on site.
- The device has three working modes, which is convenient for the user to flexibly select according to the site conditions and improve the test speed. The working modes are: fully automatic mode, manual mode, and automatic tuning manual boost mode.
- It can store and print data off-site, and the stored data number is a number, which is convenient for users to identify and find.
- When the device is automatically swept, the starting point of the frequency can be arbitrarily set within the specified range, and the large screen of the liquid crystal displays the scanning curve, which is convenient for the user to intuitively know whether to find the resonance point.
- The DSP platform technology is adopted, which can conveniently increase or decrease functions and upgrades according to user needs, and also makes the human-machine exchange interface more humanized.
Main Technical Parameters and Functions:
1 | Rated Capacity | 324kVA |
2 | The input power | Three-phase 380V voltage, frequency: 50Hz |
3 | Rated Voltage | 54kV |
4 | Rated current | 6A |
5 | Working frequency | 30-300Hz |
6 | Device output waveform | Sine wave |
7 | Waveform distortion rate | Output voltage waveform distortion rate ≤1% |
8 | Working time | Continuous 60min is allowed under rated load; Overvoltage 1.1 times 1 min |
9 | Temperature rise | Temperature rise ≤65K after continuous operation under rated load for 60min |
10 | The quality factor | Device Q≥30(f=45Hz) |
11 | Protection function | Over current, over voltage and flashover protection (see frequency conversion power supply for details) |
12 | Accuracy of measurement | Effective value of the system is 1.5 |
Working environment
1 | Environment temperature | -100oC-50oC |
2 | Relative humidity | ≤90%RH |
3 | The altitude | ≤1000m |
Exciter Transformer
1 | Rated Capacity | 9kVA |
2 | The input voltage | 0-400V,Single phase |
3 | The output voltage | 3kV |
4 | Structure | Dry type |
5 | Weight | About 50kg |
For specifications of Variable Frequency Power Supply, High voltage Reactor and Capacitor Divider, please contact us.