Introduction:
BS 476-6 is a test method of measuring the flame propagation properties of materials, primarily for fire protection performance evaluation of the walls and ceilings, measurement results are expressed as an index of flame propagation.
During the test, the specimen is exposed to the tubular torch, heat release of the lamp is 530J / S. 2 minutes and 45 seconds later, the two electric heater was adjusted to 1800 watts in total, 5 minutes after starting the test, reduced the power to 1500 watts, keep the power not changed until finishing the experiment, the total test time is 20 minutes.
To assess the flame propagation properties of the material to be tested in BS476-6, thermocouple continuous recording chimney temperature and room temperature difference, and compared the results with the calibration curve, calibration curve based on the provisions of the density of asbestos - cement slab in the same measured way.
Comparing the temperature difference value of two curves which measured at the same time. In the first three minutes of the test, take the temperature difference value every 30 seconds, in the following 4-10 minutes, take the temperature difference value every one minute. In the last 11-20 minutes, take the temperature difference value every two minutes. The flame spread index of these three periods are calculated according to formula.
I is the value of sum of the three periods flame spread index. The higher of I value, the lower the material flame retardant, 0 grade material I≤12.
Features:
Parameters:
No. | Item Name | FPT Laminated Foil Fire Propagation Index Testing Equipment |
1 | Dimension | Apparatus: 400mm (W) x 600mm x (H) x 300mm (D) |
2 | Weight | 46kg |
3 | Power supply | AC 220V, 50/60Hz, 5A |
4 | Ambient temperature | 10 ~ 35 Centigrade |
5 | Gas supply | The gas supply specified in the Standard is Standard test gas G112, as specified in BS 4947. |
6 | Flow | Gas flow for burner adjustable from 0 to 5 nl/min |
7 | Pressure | 1kPa |