KBX02 Series Explosion Proof Electrical Equipment Explosion proof Control Station
Application and Features:
Technical Parameter:
Ex marking | Gas | Il2 G Ex db eb IIC T6 Gb | Ex db eb IIC T6 Gb | Ex d e IIC T6 Gb | |||||
Dust | II2 D Ex tb IIΙC T80℃ Db | Ex tb IIΙC T80℃ Db | Ex tD A21 IP66 T80℃ | ||||||
Conformity to standards | IEC 60079-0, IEC 60079-7, IEC 60079-11, IEC 60079-31 EN 60079-0, EN 60079-7, EN 60079-11, EN 60079-31 GB3836.1,GB3836.3,GB3836.3,GB12476.1,GB12476.5 | ||||||||
Enclosure material | Enclosure | Stainless steel(Standard 304,if 316 is needed, please indicate) | |||||||
Rain shade | Bended steel plate surface powder coated, industrial grey with dark lines texture (RAL7035) | ||||||||
Exposed fastener | Stainless steel,anti-drop structure | ||||||||
Rated voltage | Max. 415V AC, 250V DC | ||||||||
Rated current | 6A,10A,16A | ||||||||
Wire diameter | ≤6A: 0.75~2.5mm² | ||||||||
6A<I≤10A: 1.5~2.5mm² | |||||||||
10A<I≤16A: 2.5mm² | |||||||||
Degree of protection | IP66 | ||||||||
Ambient temperature | -40℃〜+40/45/50/55/60/65/70℃ | ||||||||
Built-in components | K0101 explosion-proof control button. | ||||||||
K0102 explosion-proof signal lamp. | |||||||||
K0101-S explosion-proof control switch. | |||||||||
K0109 explosion-proof ammeter. | |||||||||
Installation method | Hanging type, stand type | ||||||||
Cable entries | Hanging type | M16×1.5~M63×1.5 The cable gland is not available when delivery, please indicate if necessary. | |||||||
Stand type | Only for G1 thread |
Components and Accessories:
![]() | ![]() | ![]() | ![]() |
K0101-Control button | K0101-A2 Two control button | K0102-Signal lamp | K0101-A Control button with signal lamp |
![]() | ![]() | ![]() | ![]() | ![]() |
K0109-Ammeter | K0155 Switch | φ38 Operating handle | φ65 Operating handle (padlock available) | Square operating handle |
Note: 1.Installation area of 1 pcs K0109-48 is same as 2 pcs buttons;
2.Installation area of 1 pcsφ65 operating handle or 1 pcs square operating handle is same as 2 pcs buttons;
3.Installation area of 1 pcs HL0155 switch or 1 pcs HL0109-72 is same as 2~3 buttons.
Selection Table:
Outline and Installation Dimension(Dimensions in mm):
Height of electrical accessories:
Electrical accessories | Frame of ammeter | Standard button | Double Button | Button with key | Self-lock button | Mushroom button | Mushroom button with key | Indicator light | illuminated button | Control switch S1, S3 | Control switch S2 | potentiometer (single turn) | potentiometer multi turn) |
h(mm) | 11 | 20.5 | 21.5 | 38(62) | 40 | 32 | 45(69) | 23.5 | 20.5 | 40 | 42 | 27 | 40.5 |