Ecolite Level 3 Battery Management System for Energy Storage with BAU BCU and BMU Control
Diagram of Energy storageLevel 3 Architecture System:
Level 3 battery system architecture:First level control: BAU centrally man-ages the various clusters of batteries inthe battery array, and communicateswith external PCS, UPS, EMS, airconditioning, liquid cooling, fire protec-tion, etc;
Secondary control: BCU1~BCUmmanaging each cluster of batteriescollecting cluster battery information,high-voltage control, and uploadingcluster information to BAU;
Slave control:BMU1~BMUn, responsi-ble for collecting battery voltage,temperature and otherinformation ofthe battery module.
Products | Function configuration | |||||
BCU | Parameter | MinimumValue | TypicalValue | Maximum UnitValue | Description | |
![]() | Power input | 9 | 24 | 32 | v | |
Working current | 180 | 125 | 130 | mA | ||
Rated power | S3 | W | ||||
CAN BuS | 3 | Channel | 2-wayisolation,1-way non isolation | |||
485 Bus | 2 | Channel | 2-way isolation | |||
LAN interface (TCP/P) | 1 | Channel | ||||
High edge output | 8+2 | Channel | 2-way support for PWM output | |||
Switching input detection | 9 | Channel | solaed acise dee prosive detection, 1 -way | |||
Dry node output | 2 | Channel | Rated 2A, passive output | |||
Temperature detection | 4 | Channel | +2℃℃,-40~125°℃,supports NTC-10K,100K | |||
Total voltage detection channel | 3 | Channel | 1 channel supports main and negative relayadhesion detection | |||
Total voltage detection range | 12 | 1500 | V | Total pressure detection error ≤ 0.3% | ||
Manage the rated voltage ofthe battery pack | 1500 | V | Rasrocltage ssoy, withstand voltage AC3100+,DC4380+ | |||
Supports the number of BMU | 40 | PCS | ||||
Detect the total | 6 | 500 | Strand | Used in | ||
Number of battery strings | Conjunction with BMU | |||||
Current detection | 2 | Channel | Supports 1 splitter,1 Hall(supports 5v,12v), and can collect data simultaneously | |||
Current detection range | -1500 | 1500 | A | Range optional | ||
Current detection error | 0 | 1 | 1%FSR | A | Typical error 0.5% FSR, maximum error 1% FSR | |
Insulation testing | 15% | KΩ | 0-200KΩ,error<15KΩ;>200KΩ,eror≤+15% | |||
BCU automatic addressing | support | lsolation type, level signal addressed | ||||
SOC estimation error | 0 | 3% | 5% | ≤5% | ||
SOH estimation accuracy | 0 | 3% | 10% | |||
SOE estimation accuracy | 0 | 3% | 5% |
Products | Function configuration | |||||
BAU | Parameter | MinimumValue | TypicalValue | Maximum UnitValue | Description | |
![]() | Power input | 9 | 24 | 32 | v | |
Working current | 180 | 200 | 220 | mA | ||
Rated power | ≤5 | W | ||||
CAN Bus | 4 | Channel | lsolation communication | |||
485 Bus | 4 | Channel | lsolation communication | |||
USB interface | 1 | Channel | Used for external data storage, default 32/64G | |||
LAN interface (TCP/IP) | 2 | Channel | ||||
Relay drive output (RL) | 4 | Channel | ||||
Dry node output (DO) | 4 | Channel | Rated 2A, passive dry node | |||
Digital Input (DlH) | 2 | Channel | High level detection | |||
Digital Input (DlL) | 2 | Channel | Low level detection | |||
Digital signal power input | 1 | Channel | lsolation signal detection power supply | |||
Supports the number of BCU | 30 | PCS |
Products | Function configuration | ||||
BMU | Parameter | BMU16 | BMU32 | BMU48 | BMU64 |
![]() | Working voltage range | 9~32V | |||
Working voltage range | S50mA(12V)/s25mA(24V) | ||||
Rated power | ≤0.6W | ||||
CAN communication | 1 Channel | ||||
Number of voltage acquisitionstrings | 16 | 32 | 48 | 64 | |
Temperature detection point | 4 | 8 | 12 | 16 | |
Single cell detection range | 0-5000mV; Exceeding the range of -0.5~6V can cause AFE damage | ||||
Voltage acquisition accuracy | ±5mV | ||||
Temperature detection accuracy ±2°C | ±2°C | ||||
Balance function | Support, passive balancing | ||||
Balanced number of opening routes | Every 8 channels can activate 1 channel equalization | ||||
Digital signal power input | Max120mA,effective value 30-50mA | ||||
Automatic address allocation | Support | ||||
Io output | 2-way dry contact, rated 2A, passive output | ||||
Analog input detection | 2-way (high edge detection) | ||||
Bootloader | Support CAN bus burning and writing | ||||
CAN communication | 1 Channel | ||||
Anti reverse connection of power supply | Support | ||||
Power surge prevention | Support | ||||
Voltage resistance | Voltage withstand AC3100+,DC4380+ | ||||
Working temperature | -40°C~85°C | ||||
Storage temperature | -40°C~125°C | ||||
Protection level | IP43, Not waterproof | ||||
Humidity | <95%,No condensation | ||||
Shock | ≤5500m | ||||
Automatic address allocation | At 10-25Hz,the amplitude is 1.2mm: At 26-500Hz,maximum 30m/S | ||||
Drop | 1.5m, 5 times in both horizontal and vertical directions, no damage to PCBA, no change in performance |