HV Silicone Ceramic Housing Type Metal Oxide Lightning Arrester for Power Distribution Substation
Normal operating conditions for Surge Arrester :
1. The ambient air temperature is no higher than +40°C, no lower than -40 °C .
2. The altitude above sea level does not exceed 1000m. ( the plateau area should be indicated when order.)
3. AC system frequency is 50Hz or 60Hz.
4. Power frequency voltage brought to bear on arrester for a long time does not exceed the continuous operation voltage of the arrester.
5. Maximum wind speed does not exceed 35m/s.
6. Te earthquake intensity does not exceed 7 degrees.
7. The pollution area should be indicated.
Characteristics:
Technical Data:
Type | Nominal System Voltage | Rated Voltage | Continuous Operating Voltage | MRV under 1/5 μ s Steeo Discharge Current | MRV under 8/20 μ s Lightning Discharge Current | MRV under 30/60 μ s Operating Discharge Current | Minmum Reference Voltage under 1 mA DC | 4/10 μ s High Current Impulse Twice (KA) | 2mS SW through-flow capacity A/18 | Line Discharge Class | |||
5KA | 10KA | 5KA | 10KA | 0.25KA | 0.5KA | ||||||||
Y10W5-192/500 | 220 | 192 | 150 | 560 | 500 | 426 | 280 | 100 | 800 | 3 | |||
Y10W5-200/520 | 220 | 200 | 156 | 582 | 520 | 442 | 290 | 100 | 800 | 3 | |||
Y10W5-204/532 | 220 | 204 | 159 | 594 | 532 | 452 | 296 | 100 | 800 | 3 | |||
Y10W5-216/562 | 220 | 216 | 168.5 | 630 | 562 | 478 | 314 | 100 | 800 | 3 |