24kV~40.5kV Dry Insulation Transformer Bushing
Product introduction:
Resin Impregnated Fiberfill bushing combines advantages of oil-paper bushing and RIP bushing. Advanced and imprvoed techniques make bushing better prevent from deformation, rupture and moisture absorption.
Advantage:
1/ Partial discharge is close to 0 at rated voltage;
2/ Dielectric dissipation <0.35% at rated voltage;
3/ Thermal short-time current: 25Ir, duration 2s.
Standard Technical Data:
Below info. only for your reference, all data shall be specified and determined by technical specification and customer demand.
Technical data |
Standard | IEC 60137; GB/T 4109-2008 |
Rated voltage | 24kV/40.5kV/ Customer specified |
Rated current | 630~5000A |
1min power frequency voltage withstand (Dry/ Wet) | 60/50kV; 95/80kV |
Lightning impulse voltage withstand | 125kV; 200kV |
Tanδ at 1.05Um | <0.0035 |
Partial discharge at Ur | ≤5pC |
Bending load | 3150 |
Specific Creepage distance | 31mm/kV |