Status Indicating Wire
There is a wire with status indicators for showing the operation status of the emergency lighting system and performing regular functional test.
Test button and three indicators (green, yellow and red) are in the indicating wire. Regular test on the emergency function can be simulated by the test button to make sure they will operate when required. Press and hold on the button, and to make sure they will operate when required. Press and hold on the button, and then power will be cut-off and emergency lighting operation will be activated.
Signals of the indicators are as follwing.
Green indicator:
On --- Mains supply is connected
Off --- Mains supply in disconnected
Red indicator:
On --- Battery is charging
Off --- Battery charging finished
Yellow indicator:
On --- System failure
Off --- Working
Installation of the indicating wire is to insert it in the lamp by one side. The other side with indicators sketches outside.
| Europe Standard | USA Standard | ||
---|---|---|---|---|
Order Number | CSD2S-E1 | CSD2S-E2 | CSD-E1 | CSD-E2 |
Power | 6W | 12W | 6W | 12W |
Input Voltage | AC220-240V | AC100-277V | ||
Output Voltage (to LED) | 55-80VDC | 27-38VDC | ||
Output Voltage (to battery) | 12-18VDC | |||
Input Current | 0.1A | 0.2A max | ||
Output Current | 75mA | 150mA | 160mA | 320mA |
Normal Charging Current | 200mA | 360mA | 200mA | 360mA |
Trickle Charging Current | 20mA | 30mA | 20mA | 30mA |
Storage Temperature | -40 - 85 ℃ | |||
Max. Casing Temperature | 75 ℃ | |||
Ambient Temperature | -25 - 60 ℃ |
Description | Code No. | |
Dimming Driver - Extra | 1-10V Dimming | CSD1S-X2-10 |
DALI Dimming | CSD1S-X2-DA | |
DALI PS | CSD-PS | |
Emergency Driver | with 6W output | CSD-E1 |
with 12W output | CSD-E2 | |
Emergency Battery | 1800mAh Battery | CSB1 |
3600mAh Battery | CSB2 |