1. YH5W Type Lightning Arrester Metallic Zinc-Oxide Arrester Zinc Oxide Surge Arrestor
Metal oxide arresters are the most advanced protection devices for current over-voltage. They are widely used in power generation, power transmission and distribution systems to protect the insulation of electrical equipment from overvoltage.
The organic jacket metal oxide arrester is a scientific research achievement combining the advantages of organic insulating material and traditional porcelain sleeve metal oxide arrester technology. It not only has the advantages of porcelain sleeve metal oxide arrester, but also has good electrical insulation performance and dielectric. High strength, anti-leakage, anti-corrosion, heat resistance, cold resistance, aging resistance, explosion-proof, water-repellent, good sealing performance.
2. Conditions of Use
A. Applicable to indoor and outdoor;
B. Ambient temperature -40 ℃ ~ + 40 ℃;
C. Altitude does not exceed l000m;
D. Power frequency is not less than 48Hz, no more than 62 Hz;
E. The working frequency voltage applied to the arrestor should not exceed the continuous operating voltage of the arrester (no gap type).
F. Earthquake intensity is 8 degrees and following areas;
G. The maximum wind speed does not exceed 35m / s.
3. Product type:
Y—indicating porcelain sleeve metal oxide arrester
YH(HY)—represents an organic jacket metal oxide arrester
Structural features:
W—indicating no gap
C—representing series gap
Use place:
S—indicating power distribution type
Z—representing power station type
R—representing shunt compensation capacitor
D—represents the motor T—represents the electrified railway
X—represents the line type
Additional features:
W—indicating antifouling type
G—representing high prototyping
TH—indicating wet tropics
DL—Indicating cable type lightning arrester (Advantage: The product adopts a fully sealed structure, which reduces the distance between phases and has a large creepage distance.)
Anti-fouling level:
3- indicates Class III antifouling
4. Main technical parameters
The power distribution type is used to protect the power distribution equipment such as switchgear, variable voltage, box type change, cable outlet head, and oil switch on the column from atmospheric and operational overvoltage.
Model | Nominal system voltage | Rated voltage | Continuous operation voltage | DC 1mA reference voltage | Lightning impulse current residual | Steep wave impulse current residual | switching impulse-current residual voltage | creepage distance | Height |
kV (Valid value) | KV (peak) | φ mm | H mm | ||||||
Y5WS-5/15 | 3 | 5 | 4 | 7.5 | 15 | 17.3 | 12.8 | 85 | 253 |
YH5WS-5/15 | 80 | 184 | |||||||
YH5WS-5/15DL | 80 | 184 | |||||||
Y5WS-10/30 | 6 | 10 | 8 | 15 | 30 | 34.6 | 25.6 | 85 | 253 |
YH5WS-10/30 | 80 | 184 | |||||||
YH5WS-10/30DL | 80 | 184 | |||||||
Y5WS-12/35.8 | 10 | 12 | 9.6 | 18 | 35.8 | 41.2 | 30.6 | 85 | 305 |
YH5WS-12/35.8 | 85 | 257 | |||||||
YH5WS-12/35.8DL | 85 | 257 | |||||||
Y5WS-15/45.6 | 10 | 15 | 12 | 23 | 45.6 | 52.5 | 39 | 85 | 305 |
YH5WS-15/45.6 | 85 | 257 | |||||||
YH5WS-15/45.6DL | 85 | 257 | |||||||
Y5WS-17/50 | 10 | 17 | 13.6 | 25 | 50 | 57.5 | 42.5 | 85 | 305 |
YH5WS-17/50 | 85 | 257 | |||||||
YH5WS-17/50DL | 85 | 257 |