12Vdc to 24Vdc input dry contact pir infrared sensor with surface mounting
1. Features
1) PIR motion detection
2) Accurate NO/NC dry contact output
3) Daylight sensor detection available
4) Detection area, hold time, and daylight threshold can be set by remote/DIP switch
5) Max detection range: 5-8m in diameter
6) The factory setting is NO (normally open) dry contact, yet can switch to NC (normal close) by remote
7) Hallway and Toilet motion detection is highly recommended
8) Compacted mini size for perfect ceiling mounting
2. Parameters
Input/Output | Input voltage | 12-24V DC |
Rated voltage | 12/24V DC | |
Working current | 20mA max | |
Power consumption | ≤0.5W @12/24V DC | |
Output signal | NO/NC dry contact (Factory setting is NO dry contact) | |
Sensor parameter | Function | PIR motion detection+ daylight sensor |
Detection Area | DIP or remote setting: 100%/75%/50%/25% | |
Hold Time | DIP: 5s/1min/3min/5min/10min/30min MH10remote: 5s/30s/1min/3min/5min/10min/20min/30min | |
Daylight Sensor | DIP: 50Lux/Disable MH10remote: 5Lux/15Lux/30Lux/50Lux/ 100Lux/150Lux/Disable | |
Radius detection range(based on 100% sensitivity) | 2.5-4m based on 3m mounting height | |
Remote control | Available | |
Mounting height | 2.5-4m typical value:3m | |
Application environment | Installation | Surface mounting |
Working temperature | 0℃...+35℃ | |
Storage temperature | -40℃~+80℃ | |
Certificate Standard | Certificate | Compliant to CE |
Environmental requirements | Compliant to RoHS | |
IP rating | IP20 | |
“N/A” means not available |
3. Dimension
4. Wiring Diagram & Function
5. Start Process & Initialization
When powered on, the sensor indicator will turn off after flashing for 10S and will not detect a moving signal during this time. After 10S,you can use our MH10 remote or dip switch to adjust detection area, hold time, daylight sensor etc
6. Factory Settings
Detection Area: 100% Hold Time: 5s Daylight Sensor: Disable
7. Detection radiation
8. DIP Settings
Detection Area
1 | 2 | |
100% | ON | ON |
75% | - | ON |
50% | ON | - |
25% | - | - |
Hold Time
3 | 4 | 5 | 6 | ||
Ⅰ | ON | ON | ON | ON | 5S |
Ⅱ | ON | - | ON | ON | 1min |
Ⅲ | ON | ON | - | ON | 3min |
Ⅳ | ON | ON | ON | - | 5min |
Ⅴ | ON | ON | - | - | 10min |
Ⅵ | - | - | ON | ON | 20min |
Ⅶ | - | - | - | - | 30min |
Daylight Sensor
7 | 8 | 9 | ||
Ⅰ | ON | ON | ON | 5Lux |
Ⅱ | - | ON | ON | 50Lux |
III | ON | - | ON | 100Lux |
Ⅳ | ON | ON | - | 150Lux |
Ⅴ | - | - | - | Disable* |
**Once the daylight sensor is set as Disable, our motion sensor will detect human movement regardless of the environment lux
10. Remote Control