DC Motion Sensor MC079D RC3 with Plug-in Design and Daylight Priority Function
Easy Upgrading For Warehouse High Bay Lights
1. Features
2. Parameter
Input | ||
DC Input Voltage | 12/24V DC ±1V | |
Rated Voltage | 12/24V | |
Stand-by Power | <0.3W | |
Wiring | Screw terminals | |
Output | Working Mode | 0-10V DC |
Wiring | Screw terminals | |
Dim Interface | 0-10V Dimming | < 50mA (Non-constant source) |
Sensor Parameters | Operating Frequency | 5.8 GHz ±75 MHz,ISM Band. |
Transmitting power | 1mW Max. | |
Hold time | 5S/30S/1min/3min/5min/10min/20min/30min | |
Stand-by DIM Level | 10%(1.4-1.6V), 20%(1.9-2.1V), 30%(2.9-3.1V), 50% (4.9-5.1V) | |
Stand-by Period | 0s/10S/1min/3min/5min/10min/30min/+∞ | |
Detection Area | 25%/50%/75%/100% | |
Daylight Sensor | Daylight threshold: 5lux/15Lux/30Lux/50Lux/100lux/150lux/Disable Daylight priority: ON/OFF value (5lux/15Lux/30Lux/50Lux)/150Lux 100Lux/200Lux 150Lux/300Lux | |
Detecting Radius | See detection pattern | |
Mounting Height | 15m Max | |
Detecting Angle | 150°(wall mounting) 360°(ceiling mounting) | |
Operating Environment | Operating Temperature | -35℃…+70℃ |
Storage Temperature | Temperature: -40℃…+80℃; Humidity: 10%-95% (non-condensing) | |
Certificate Standards | Safety standards | EN60669-2-1, EN60669-1 |
EMC standards | EN55015, EN61000-3-2, EN61000-3-3, EN61547 | |
Environmental Requirement | Compliant to RoHS | |
Certificate | NA | |
IP Rating | IP65 | |
Protection Class | Class II | |
Installation | External mounting,integrated mounting | |
Dimension | See dimension | |
Package | White paper box | |
Net Weight | 55g | |
Lifetime | 50,000h @Ta 230V full load | |
Note 1. “N/A”means not available. 2. Detection area is effected on volume of motion object and motion speed. The detection area is tested by a 165cm height person and walking speed is 0.5m/s. |
3. Function
1) On/OFF Function (stand-by period be set to “0”s)
2) 2-step dimming function (stand-by period be set to “+∞”)
3) 3-step dimming function (stand-by period be set to “10s/1min/3min/5min/10min/30min”)
4) Daylight priority(stand-by period set to +∞)
4. Dimension (mm)
5. Wiring
*The sensor is designed for connect one load only. Connect more than one loads may damage the sensor.
6.Structure
7. Installation
8. Radiation Pattern
Ceiling mounting
*Only 100%/75%/50% detection sensitivity is workable when installed at 15m mounting height. 25% sensitivity is not able to detect motion signal.
Wall mounting
9. Remote Control