【Product Features】
【Parameters】
Input | ||||
Rated Voltage | 120/277V AC 50/60Hz(US);220-240VAC 50/60Hz(Europe) | |||
Stand-by Power | ≤0.5W | |||
Surge Test | 1kV(L/N,EN61000-4-5) | |||
Output | ||||
Output Control | ON-OFF | 0-10VDC Dimming Signal | ||
Load Capacity | 4A @120Vac 3A @277Vac | |||
Max. Surge Capacity | 50A (50% Ipeak, twidth =200us, 230Vac full load, cold start); | |||
0-10VDimming | < 50mA (Non-constant current source) 10%(1.4-1.6V) 20%(1.9-2.1V) 30%(2.9-3.1V) 50% (4.9-5.1V) | |||
Sensor Parameter | ||||
Operating Frequency | 5.8 GHz ±75MHz, ISM wave band. | |||
Transmitting power | 3mW Max. | |||
Hold time | 5S/30S/1min/3min/20min/30min/60min(setting by DIP) | |||
5s/30s/1min/3min/5min/10min/20min/30min (setting by remote) | ||||
Stand-by dim Level | 20%(1.9-2.1V)/30%(2.9-3.1V)(setting by DIP) | |||
10%(1.4-1.6V)/20%(1.9-2.1V)/30%(2.9-3.1V)/50%(4.9-5.1V)(setting by remote) | ||||
5s/30s/1min/3min/5min/10min/20min/30min (setting by remote) | ||||
Stand-by Period | 0S/5S/5min/10min/30min/60min/+∞(setting by DIP) | |||
0s/10s/1min/3min/5min/10min/30min/+∞ (setting by remote) | ||||
Detection | 100%/75%/50%/25%(setting by DIP) | |||
100%/75%/50%/25% (setting by remote) | ||||
Daylight Sensor | Daylight threshold | 5lux/15lux/30lux/50lux/100lux/150lux/Disable | ||
5lux/15lux/30lux/50lux/100lux/150lux/Disable (setting by remote) | ||||
Daylight priority | ON | Off | ||
5lux/15lux/ 30lux/50lux | Turn on Value+(50-150Lux) | |||
100lux | Turn on Value+(50-150Lux) | |||
150lux | Turn on Value+(50-150Lux) | |||
Detecting Radius | ceiling mounting12m r≥3m@1m/s, 39.4ft r≥10ft@3.28ft/s Testing condition: 100% sensitivity, open 60㎡ indoor area. | |||
Mounting Height | 12m(15m Max )(39.4ft Max 49.2ft) | |||
Environment | ||||
Operating Temperature | -25~60°C(-13~140°F) | |||
Storage Temperature | -40℃~80℃(-40~176°F), Humidity: ≤85%(Non-condensing) | |||
Certificate Standard | ||||
Certificate | UL(pending) CE | |||
Environmental Requirement | Compliant to RoHS 2.0, Reach | |||
Safety standards | EN61058-1,UL60703-1 | |||
EMC standards | EN300440; EN301489-1; EN55015; EN61547; EN61000-3-2; EN61000-3-3; EN62479 | |||
IP Rating | IP20 | |||
Product Class | Class Ⅱ | |||
Other | ||||
Wiring | AC wire:(L:Black;N:White;L’:Red) 1-10V:(GND:Pink;10V:Purple) | |||
Installation | Built-in | |||
Package | Bubble bag + Clapboard + Carton(K=A) | |||
Net Weight | 129.4±5g | |||
Lifetime | 5 years warranty @Ta |
【Function】
ON-OFF function | Stand-by Period be set “0s” |
2-step dimming | Stand-by Period be set “+∞” |
3-step dimming | Stand-by Period be set “5S/5min/10min/30min/1h” |
Daylight priority | Stand-by Period be set “+∞” |
【Product Information】
【Wiring diagram】
*The sensor is designed for connect one load only. Connect more than one loads may damage the sensor.
【Installation Instruction】
【Detection Range】
【Remote Control】
【Initialization】
After power on, the sensor automatically turns on light to 100% brightness and turns off light in 10seconds. During initialization, sensor is not able to detect movement.
【Default setting】
Sensitivity: 100%, Hold time: 5s, Daylight sensor: Disable, Stand-by Period: 0s, Stand-by DIM Level:20%
【Application Notice】