Electric Equipment Troubleshooting YC1891D-24 Single Phase Meter Test Bench
Product Description
- Meters under testing: 1P2W
- Testing mode active power, reactive power With MSVT, can test single phase meters with closed links between the current and voltage measuring circuits(I-P links) With current output switch, can calibrate 2-element meters (optional)
- Installing Rs232 Ethernet communication ports in each meter position, to realize automatic calibration of electronic meters (optional)
- The meter test systems can measure mechanical meters, electronic mechanical meters and electronic meters by the way of automatic, semi-automatic or manual operation
- Aluminum alloy material, light and strong and corrosion resistant
- Automatic positioning rotor mark of disc of mechanical meters, with more efficiency.
- The swing together of the scanning heads simplifies the control
- Starting test and creeping test
- Measuring different constants of meters synchronously
- With the protection function of overload, short voltage circuit and open current circuit
- The testing software with friendly Window 10 and XP operation system, includes functional module of all kinds or modern energy meter needed, to reality error test, harmonic test, demand test, influence test etc.
- The stored testing data can be transferred to multi-format for other program use
- The whole system is accredited to conforms to EU health and safety standards with CE certificate
Product Parameters
| YC1891D-6 | YC1891D-12 | YC1891D-24 | YC1891D-48 |
Number of meter positions | 6 | 12 | 24 | 48 |
Accuracy | 0.05 |
Power Source | YCS-101-250 | YCS-101-600 | YCS-101-1200 | YCS-101-2500 |
Standard Meter | SZ01A-K3 |
MSVT | HJ200GL-6 | HJ200GL-12 | HJ200GL-24 | HJ200GL-48 |
QCD | D5 series |
Scanning Head | YCG-2 series |
Voltage |
Test voltage output | 24V – 288V or customized |
Power of the voltage output | 100VA | 250VA | 500VA | 1000VA |
Resolution | Better than 0.01% of full scale value of range |
Setting accuracy | Better than 0.05% at the final range value |
Stability | Better than 0.005%/h (integration time 150 s) |
Load regulation from 0-max. load | Better than 0.01% |
Distortion factor | Better than 0.3% for linear resistance load |
Harmonics | 2nd – 21st free programmable |
Current |
Test current output | 1mA – 100A or customized,Max.200A | 1mA – 100A |
Power of the current output | 150VA | 350VA | 750VA | 1500VA |
Resolution | Better than 0.01% of full scale value of range |
Setting accuracy | Better than 0.05% at the final range value |
Stability | Better than 0.005%/h (integration time 150 s) |
Load regulation from 0-max. load | Better than 0.01% |
Distortion factor | Better than 0.3% for linear resistance load |
Harmonics | 2nd – 21st free programmable |
Phase angle |
Range | 0 -- 360° |
Resolution | 0.01° |
Setting accuracy | 0.1° |
Frequency |
Range | 45Hz – 65Hz |
Resolution | 0.01Hz |
Error display |
Type of error display | Red LED |
Resolution of the error displays | 8 digits |
|
Voltage Supply | 220V±10% or customized 50/60Hz±2Hz | 3x220/380V±10% or customized 50/60Hz±2Hz |
Ambient temperature | -10°C -- +40°C |
Relative humidity | 35% -- 85% |
Our Advantages
- We have been engaged in the Electric Energy Meter measurement field for over twenty years as an all-time technological leader and creator of new technology in the Electric Energy Meter calibrator field. We have an excellent R&D team that has devoted to the technical development of Electric Energy Meter test instruments for a long time, we can satisfy different requirements of all kinds of customers.
- All of our staff have received specialized training and acquired good professional quality and skills. The company adopts ISO9001 management and we have passed the authentication of ISO9001-2000 in 2002 and all staff has taken TQM training. Yangcheng has now realized ISO9001 control of R&D production, marketing & sales, and service completely to guarantee product quality.
- We have a consummate marketing network and we offer a competitive price.
- Our well-trained service team is able to provide maintenance, training, scheme design, and software update services to each customer for the first time.