1. High Accuracy and Stability Output:
The device boasts exceptional precision and unwavering stability in its output, ensuring reliable performance across various applications.
2. RS232 Interface for Automated Operation:
Equipped with an RS232 interface, the device facilitates seamless automated operation, allowing for efficient communication and control with compatible systems.
3. Optional Keyboard for Manual Operation:
For added versatility, users have the option of incorporating a keyboard, enabling manual operation when desired. This feature provides flexibility in control methods to suit diverse operational preferences.
4. Programmable 2nd to 21st Harmonic Output:
Offering extensive programmability, the device allows users to tailor output characteristics such as harmonic range, amplitude, and phase, empowering precise customization to meet specific requirements.
5. Lightweight and Durable Aluminum Alloy Construction:
Crafted from high-quality aluminum alloy materials, the device combines lightweight portability with robust durability, effectively resisting corrosion and ensuring long-lasting performance in various environmental conditions.
6. Protective Functions against Overload and Circuit Interruptions:
Integrated with advanced protective mechanisms, including overload protection, short voltage circuit protection, and open current circuit protection, the device safeguards against potential hazards, enhancing operational safety and equipment longevity.
7. Intuitive Control Software for Effortless Operation:
Featuring user-friendly control software, the device offers a simple and intuitive interface, facilitating easy operation and enhancing user convenience. With streamlined functionality, users can efficiently navigate settings and commands, optimizing workflow efficiency.
Application Conditions and Requirements | |||||
Environment | Power Requirement | Safety | |||
Operation | Humidity | Altitude | Voltage Supply | IP Class | Conformity |
Temperature | |||||
-10°C--+40ºC | 35%--85% | <2500m | 3x220/380V±10% | IP30 | CE conform |
(or customized) | |||||
50/60Hz±2Hz | |||||
Type | YCS-103-250 | YCS-103-800 | YCS-103-1200 | YCS-203-2500 | |
Voltage | |||||
Test voltage output(Phase-Neutral) | 3x(24V-300V)(or customized) | ||||
Power of the voltage output | Max.3x100VA | Max.3x250VA | Max.3x500VA | Max.3x1000VA | |
Resolution | Better than 0.01%of full scale value of range | ||||
Setting accuracy | Better than 0.05% at the final range value | ||||
Stability | Better than 0.005%/h(integration time 150 s) | ||||
Load regulation from 0-max.load | Better than 0.01% | ||||
Distortion factor | Better than 0.3% for linear resistance load | ||||
Harmonics | 2nd-41st free programmable | ||||
Current | |||||
Test current output | 3x(1mA-120A/200A) | ||||
Power of the current output | Max.3x250VA | Max.3x500VA | Max.3x1000VA | Max.3x2000VA | |
Resolution | Better than 0.01% of full scale value of range | ||||
Setting accuracy | Better than 0.05%at the final range value | ||||
Stability | Better than 0.005%/h(integration time 150 s) | ||||
Load regulation from 0-max.load | Better than 0.01% | ||||
Distortion factor | Better than 0.3% for linear resistance load | ||||
Harmonics | 2nd-41st free programmable | ||||
Phase angle | |||||
Range | 0-360° | ||||
Resolution | 0.01° | ||||
Setting accuracy | 0.1° | ||||
Frequency | |||||
Range | 45Hz-65Hz | ||||
Resolution | 0.01Hz | ||||
Error display | |||||
Type of error display | Red LED | ||||
Resolution of the error displays | 8 digits |