Single Core Conductor Mineral Insulated Cable Heating Element of 600 V Rate
Single Core Conductor Mineral Insulated Cable Heating Element of 600 V Rate is designed and fabricated heating element to be used on 600 v power or lower access with a single core conductor in the cable so that the element design should be limited to A, B, C type.
Heating Cable Specification (600V Single Conductor)
Cable Code | Diameter | HDPE Diameter | Standard resistance value at +20℃ | Maximum Production Length | Unit weight |
mm | mm | Ω/m | m | kg/km | |
16C1.7 | 8.2 | 10 | 0.0017 | 350 | 366.54 |
16C2.2 | 7.6 | 9.4 | 0.0022 | 380 | 307.77 |
16C2.9 | 7.0 | 8.8 | 0.0029 | 400 | 264.45 |
16C4 | 5.9 | 7.7 | 0.004 | 600 | 190.88 |
16C7 | 5.3 | 7.1 | 0.007 | 600 | 154.08 |
16C11 | 4.9 | 6.7 | 0.011 | 600 | 132.25 |
16C13 | 4.6 | 6.4 | 0.013 | 600 (300)☆ | 125.7 |
16C17 | 4.6 | 6.4 | 0.017 | 600 (300)☆ | 117.16 |
16C21 | 4.6 | 6.4 | 0.021 | 600 (300)☆ | 111.9 |
16C25 | 3.7 | 5.5 | 0.025 | 600 (480)☆ | 68.83 |
16C33 | 3.7 | 5.5 | 0.033 | 600 (480)☆ | 63.76 |
16C40 | 3.4 | 5.2 | 0.04 | 600 (560)☆ | 58.87 |
16C63 | 3.2 | 5 | 0.063 | 600 | 51.47 |
16K80 | 6.8 | 8.6 | 0.08 | 370 (140)☆ | 254.18 |
16K100 | 5.2 | 7 | 0.1 | 450 (240)☆ | 162.11 |
16K140 | 4.9 | 6.7 | 0.14 | 600 (270)☆ | 122.55 |
16K197 | 4.45 | 6.25 | 0.197 | 600 (330)☆ | 111.32 |
16K220 | 4.5 | 6.3 | 0.22 | 600 (330)☆ | 102.89 |
16K315 | 4.3 | 6.1 | 0.315 | 600 (350)☆ | 91.44 |
16K345 | 4.2 | 6.0 | 0.345 | 600 (370)☆ | 85.9 |
16K450 | 4.0 | 5.8 | 0.45 | 600 (400)☆ | 80.73 |
16K630 | 4.0 | 5.8 | 0.63 | 600 (400)☆ | 77.26 |
16K800 | 3.5 | 5.3 | 0.8 | 600 (530)☆ | 61.48 |
16K1250 | 2.8 | 4.6 | 1.25 | 600 | 40.83 |
16K2000 | 2.8 | 4.6 | 2.0 | 600 | 38.96 |
Mineral insulation Heating Element is to be designed based on selection of mineral insulated heating cable which is prefabricated in the manufacturer's workshop into a heating element that can be directly connected to the power supply. It is usually composed of heating cables, cold and hot joints, cold end cables, terminals, tail ends and lead wires, etc. Type A, B and C are only suitable for single-core heating cable. It can be widely used on heating or heat tracing of process conveying pipes and accessories, pumps, reactor, cracking furnace, carburetor, flash evaporator, storage tank, storage tank, other devices and vessels etc.
Common structure of the heating cable for the heating element is of single core and two core, while the customization can be according to clients’ needs to design and provide MI heating cable of three core or more.
The CML IEC Ex and ATEX explosion-proof certificates have granted for the mineral insulated heating cable products
.