158T 117T 184T 198T 257T Bitmain Mining Machine Bitcoin Miner S19 Hydro
Bitcoin Miner S19 Hydro 151.5T S19 Pro Hydro 158T 117T 184T 198T S19XP Hyd 257T Bitmain Mining Machine
Sales Tina: W,echat and Wh.at.s.app : +86-18823390532 Te.leg.ram: @tinaletine
NOTES
1. The ANTMINER S19 Pro+ Hyd. is recommended to be used simultaneously with the ANTSPACE HK3.
Specification:
Product Glance |
|
Version | S19 Pro+ Hyd. |
Model No. | j0-10 |
Crypto Algorithm | SHA256 |
Hashrate, TH/s | 198 ±3% |
Power on wall @35°C, Watt(1-1) | 5445 ±5% |
Power efficiency on wall @35°C, J/TH(1-1) | 27.5 ±5% |
Detailed Characteristics |
|
Power supply AC Input voltage, Volt(2-1) | 342~418 |
Power supply AC Input Frequency Range, Hz | 47~63 |
Power supply AC Input current, Amp(2-2) | 30 |
Hardware Configuration |
|
Networking connection mode | RJ45 Ethernet 10/100M |
Miner Size (Length*Width*Height, w/o package),mm | 410*196*209 |
Miner Size (Length*Width*Height, with package),mm | 570*316*430 |
Net weight, kg | 15.2 |
Gross weight, kg | 17.5 |
Specification Details For ANTSPACE HK3 | |
Product Overview |
|
Version | ANTSPACE HK3 |
Dimensions (L*W*H) (mm) | 6058*2438*2896 |
Miner Capacity | 210 units -S19 Hyd. Series miner |
Container Certification | China Classification Society Certification |
Safety Certification | North America/Standards:NFPA 79:2021,UL 508A:2018 R8.21, |
CSA C22.2 No. 14-18,ANSI/ISO 12100:2012 | |
EU/Standards:EN ISO 12100,EN 60204-1 | |
Operating Power(kW) | 1047~1050 |
PUE(Power Usage Effectiveness) | 1.022(Excluding cooling tower)/1.036(Including cooling tower) |
Input Voltage and Frequency | 415V±5% 60Hz(North America) |
400V±5% 50Hz(EU,Middle East) | |
Detailed Characteristics |
|
Shipping Weight(T) | 8 |
Operating Weight (T) | 12 |
Main Switch of Power Distribution Cabinets(A) | 1200(North America) |
1250(EU,Middle East) | |
Rated Current(A) | 952 |
Standard Power(kW) | 1049 |
Maximum Power(kW) | 1050 |
Rated Current per Miner(A) | 10 |
Inlet Cable | The inlet cables can withstand high-voltage of above 600V, with the following requirements per phase: |
L1 single core cable 600kcMil(300mm²)x4 | |
L2 single core cable 600kcMil(300mm²)x4 | |
L3 single core cable 600kcMil(300mm²)x4 | |
N Single-core cable 600kcMil(300mm²)x4 | |
PE single-core cable 500kcMil(240mm²)x2 | |
Connection Interface(Cooling Tower) | DN125(GB/T 9119-2010 PN16 DN125) |
Connection Interface(Plate Heat Exchage Interface) | DN100(GB/T 9119-2010 PN16 DN100) |
Flow Rate(m³/h) | >85 |
Quantity of ANTSPACE powered by one 2500kVA Transformer | 2 |