LIRUISI Communication Battery 2V 300Ah Valve Regulated Sealed Lead-Acid Battery LT-3000
Product introduction:
Good vibration resistance: the fully charged state is that the battery is completely fixed, with an amplitude of 4mm, a frequency of 16.7HZ vibration for 1 hour, no leakage, no battery expansion and rupture, and the open circuit voltage is normal.
Good safety performance: no electrolyte leakage under normal use, no battery expansion and rupture.
Good over-discharge resistance: 25 degrees Celsius, fully charged battery for 3 weeks of constant resistance discharge (resistance is only equivalent to the resistance required by the battery's 1CA discharge) The recovery amount is more than 75%.
Good impact resistance: the fully charged battery naturally falls from a height of 20cm to a 1cm thick hardwood board 3 times without leakage, no battery expansion and rupture, and the open circuit voltage is normal.
Good charging resistance: 25 degrees Celsius, fully charged battery 0.1CA charge for 48 hours, no leakage, no battery expansion and rupture, open circuit voltage is normal, capacity maintained above 95%.
Good resistance to large current: fully charged battery 2CA discharge for 5 minutes or 10CA discharge for 5 seconds, no conductive part fused, no appearance deformation.
Good discharge performance: stable discharge voltage and stable discharge platform.
LT series 2V valve regulated sealed lead-acid battery series product specifications:
Model | standard voltage | capacity(Ah) | size(mm) | |||||
10HR | 10HR | Length (L) | Width (W) | High (H) | TH | Weight (kg) | ||
LT-3000 | 2 | 3000 | 1950 | 712 | 712 | 340 | 383 | 212 |
Installation, use and maintenance
Precautions:
The battery is shipped with liquid and must not attempt to disassemble the battery to avoid danger. If the battery case is accidentally damaged and contact sulfuric acid, please rinse with plenty of water, and seek medical attention immediately if necessary
Connection of batteries:
Batteries or battery packs with the same actual capacity can be used in series
Battery charging:
Float charge (limit voltage, control current) use: charging voltage 2.275-2.30V/single cell, temperature compensation, temperature
Storage and Installation:
The battery that is not in use should be removed from the connecting cable, covered with the pole sheath and wiped clean