LIRUISI Power Frequency Machine Room Power Supply Black HP Series 250KVA
Product Introduction:
UPS power supply is a power supply device used to protect computers, servers, network equipment and other electronic devices. UPS power supply can provide a stable power supply for these devices, keep the equipment running in the event of unstable power supply or power failure, and ensure that the equipment shuts down normally, so as to avoid data loss and equipment flash failure. UPS power supply is usually composed of battery pack, charger, inverter, intelligent controller, etc., and the higher-end UPS power supply will also be equipped with network management functions, which can remotely monitor and manage the operating status of UPS power supply and improve the management efficiency of equipment.
How it works:
Three-in, three-out, double-conversion online working power frequency machine operation.
Product parameters:
HP10KVA-HP400KVA [Power frequency tower three-in, three-out UPS system] | |
Model | HP250KVA |
Nominal capacity (KW) | 200 |
Single-phase input maximum current (A) | 475 |
Working method and principle | In-line power supply, static bypass switch (non-stop switching), double conversion technology, the output power supply is completely isolated |
Input power factor | 0.8/0.9 (12 pulses)/0.95 (with active filter) |
Phase number | Three-phase + N + G |
Nominal voltage | 380VAC±25% |
Nominal frequency | 50HZ±10%,60HZ±10% |
voltage harmonic distortion | <5% |
soft start | 0~100% 5 sec |
HP10KVA-HP400KVA [Power frequency tower three-in, three-out UPS system] battery | |
Maximum discharge current (A) | 568 |
Number of batteries per group | 12V type 32 sections or 2V type 192 sections |
Nominal battery voltage | 384VDC(348V-384V);160~400KVA:384/396VDC |
float voltage | 432VDC |
charging current | 6~ 30A (adjustable) |
HP10KVA-HP400KVA [Power frequency tower three-in, three-out UPS system] bypass | |
Phase number | Three-phase + N + G |
Nominal voltage | 380VAC±15% |
Nominal frequency | 50HZ±5%;60HZ±5% |
Transition time | 0ms |
HP10KVA-HP400KVA [Power frequency tower three-in, three-out UPS system] overall system | |
Communication interface | RS232, RS485, Dry Contacts, Smart Slots |
Operating temperature | 0~40℃ |
Relative humidity (non-condensing) | 0%~90% |
Operating height (max) | < 1000 meters (1% decrease in power for each additional 100 meters, up to 4000 meters) |
Cooling method | forced ventilation |
Protection class | IP20 |
Box color | White or black |
Easy to maintain | Front/top/side |