LIRUISI Communication Battery 2V 800Ah Valve Regulated Sealed Lead-Acid Battery LT-800
Product introduction:
Good over-discharge resistance: 25 degrees Celsius, fully charged battery for 3 weeks of constant resistance discharge (resistance is only equivalent to the resistance required by the battery's 1CA discharge) The recovery amount is more than 75%.
LT series 2V valve regulated sealed lead-acid battery series product specifications:
Model | standard voltage | capacity(Ah) | size(mm) | |||||
10HR | 10HR | Length (L) | Width (W) | High (H) | TH | Weight (kg) | ||
LT-800 | 2 | 800 | 520 | 410 | 410 | 328 | 365 | 64 |
Installation, use and maintenance
Precautions:
Check regularly (once a year) whether the connecting wire is loose, and if there is looseness, it should be tightened
Battery charging:
1. Float charge (limit voltage, control current) use: charging voltage 2.275-2.30V/single cell, temperature compensation, temperature compensation coefficient per unit is 3mv (based on 20)
2. When trickle is used, the battery float charge current is high speed to less than 2Ma/Ah
Connection of batteries:
The batteries of the battery pack should be spaced more than 10mm apart to facilitate heat dissipation
Storage and Installation:
The battery should be stored in a dry and ventilated place, away from direct sunlight and away from heat sources