LIRUISI Communication Battery 2V Valve Regulated Sealed Lead-Acid Battery LT-300
Product introduction:
UPS lead-acid battery is composed of lead and electrolyte. During charging, the electrolyte is decomposed into oxygen and hydrogen, while metallic lead is precipitated at the negative electrode, and a redox reaction occurs in the positive electrode reaction, eventually converted to lead oxides.
LT series 2V valve regulated sealed lead-acid battery series product specifications:
Model | standard voltage | capacity(Ah) | size(mm) | |||||
10HR | 10HR | Length (L) | Width (W) | High (H) | TH | Weight (kg) | ||
LT-300 | 2 | 300 | 195 | 252 | 152 | 328 | 365 | 22 |
Installation, use and maintenance
Battery charging:
1. Float charge (limit voltage, control current) use: charging voltage 2.275-2.30V/single cell, temperature compensation, temperature compensation coefficient per unit is 3mv (based on 20)
2. When trickle is used, the battery float charge current is high speed to less than 2Ma/Ah
Storage and Installation:
1. The battery that is not in use should be removed from the connecting cable, covered with the pole sheath and wiped clean
2. Maintain and charge the battery every three months, the charging method is the current limiting and constant voltage method, the initial charging current is 0.1CA, and the charging voltage is 2.4V/single cell
Connection of batteries:
1. Batteries or battery packs with the same actual capacity can be used in series
2. Cells or battery packs with the same actual voltage can be used in parallel
3. The connection part should be tight to prevent sparks; If the contact is poor, the contact surface can be cleaned with soda
Precautions:
1. The battery is shipped with liquid and must not attempt to disassemble the battery to avoid danger. If the battery case is accidentally damaged and contact sulfuric acid, please rinse with plenty of water, and seek medical attention immediately if necessary
2. Do not mix new and old batteries
3. Do not use batteries in sealed containers