Product introduction:
Good charging resistance: 25 degrees Celsius, fully charged battery 0.1CA charge for 48 hours, no leakage, no battery expansion and rupture, open circuit voltage is normal, capacity maintained above 95%.
LT series 2V valve regulated sealed lead-acid battery series product specifications:
Model | standard voltage | capacity(Ah) | size(mm) | |||||
10HR | 10HR | Length (L) | Width (W) | High (H) | TH | Weight (kg) | ||
LT-1000 | 2 | 1000 | 650 | 475 | 475 | 328 | 365 | 75 |
Installation, use and maintenance
Battery charging:
The maximum current shall not exceed 25% of the nominal capacity
Note: The battery should not be used in a closed or high temperature environment and should be kept away from fire
Precautions:
The battery should have a complete resume, including factory date, installation date, operation record, etc
Connection of batteries:
The positive and negative poles shall not be reversed or short-circuited
Storage and Installation:
The battery that is not in use should be removed from the connecting cable, covered with the pole sheath and wiped clean
Maintain and charge the battery every three months, the charging method is the current limiting and constant voltage method, the initial charging current is 0.1CA, and the charging voltage is 2.4V/single cell