LIRUISI Communication Battery 2V 600Ah Valve Regulated Sealed Lead-Acid Battery LT-600
Product introduction:
Good charging resistance: 25 degrees Celsius, fully charged battery 0.1CA charge for 48 hours, no leakage, no battery expansion and rupture, open circuit voltage is normal, capacity maintained above 95%.
LT series 2V valve regulated sealed lead-acid battery series product specifications:
Model | standard voltage | capacity(Ah) | size(mm) | |||||
10HR | 10HR | Length (L) | Width (W) | High (H) | TH | Weight (kg) | ||
LT-600 | 2 | 600 | 390 | 301 | 301 | 328 | 365 | 46.5 |
Installation, use and maintenance
Precautions:
Regularly (once every three months) wipe the battery with a soft fabric to keep the battery clean
Battery charging:
1. Float charge (limit voltage, control current) use: charging voltage 2.275-2.30V/single cell, temperature compensation, temperature compensation coefficient per unit is 3mv (based on 20)
2. When trickle is used, the battery float charge current is high speed to less than 2Ma/Ah
3. Cycle use (full and stop, discharge and charge): charging voltage 2.35-2.45V/single cell
4. The maximum current shall not exceed 25% of the nominal capacity
Note: The battery should not be used in a closed or high temperature environment and should be kept away from fire
Storage and Installation:
1. The battery that is not in use should be removed from the connecting cable, covered with the pole sheath and wiped clean
2. Maintain and charge the battery every three months, the charging method is the current limiting and constant voltage method, the initial charging current is 0.1CA, and the charging voltage is 2.4V/single cell
Connection of batteries:
The batteries of the battery pack should be spaced more than 10mm apart to facilitate heat dissipation