LIRUISI Modular Data Center Dual-Row Integrated Machine Room Dedicated Model N
Product introduction Of Modular Data Center
Adopts high integration and high standard design, including cabinet, cold aisle, power supply and distribution, cooling, management and other five systems.
Application scenarios Of Modular Data Center
Core business equipment rooms such as large-scale data centers and campus data centers are suitable for Government, medical, education, finance, telecommunications and other leasing and self-use business.
Product parameters Of Modular Data Center
Model N | 25-150 |
phase | Three-phase four-wire input/three-phase four-wire output |
capacity |
150KW |
Power module capacity | 25KW |
Number of power modules that can be installed | 6 |
input | |
rated voltage | 3X380VAC/400VAC/415VAC (3 phase + N) |
Voltage range | 100% load 305 ~ 478 VAC ; < 70% load 208 ~ 304VAC |
Rated frequency | 50/60HZ (automatic selection) |
Frequency range | 40 ~ 70HZ |
Input power factor | 100% load > 0.99 ; 50% load >0.98 |
Current Harmonic Loss (THDi) | < 3% @100% load |
output | |
rated voltage | 3X380VAC/400VAC/415VAC (3 phase+N) |
Voltage stability (steady state) | ≤ 1% typical (balanced load); ≤ 2% typical (unbalanced load) |
Voltage stability (Shun state) | ≤ ± 5% typical value |
Rated frequency |
50/60HZ |
Frequency Range (Synchronous Correction Range) | 46 ~ 54HZ /56 ~ 64HZ |
Frequency range (battery mode) | 50/60 HZ士1% |
overload capacity | 110% 60 minutes, 120% 10 minutes, 150% 60 seconds, >150% 200ms |
Overload Capability Harmonic Distortion (THDV) | ≤ 1.5% THD (linear load) ; ≤ 4% THD (Nonlinear Load) |
efficiency | Up to 94.5% |
Battery/Charge | |
rated voltage | 216V (12VX36 pieces) |
Maximum voltage | 240V (12VX40 pcs) |
Lowest voltage | 192V (12VX32 pieces) |
float voltage |
2.25V / Cell |
High charging voltage |
2.35V / Cell |
temperature compensation | Yes. |
Maximum charging current | 8A |
physical properties | |
Dimensions: Width X Depth X Height (mm) |
600X1200X2000 |
355 |
|
Use environment |
|
temperature and humidity | 0-40" C ; 0-95% relative humidity (non-condensing) |
elevation | < 1000m rated power |
IP protection class | IP 20 |
Control management | |
Smart RS-232/USB | Supports Wind0WS@ 2000/2003/XP/ViSta/2008, Wind0WS@ 7/8, LinuX and MAC |
Optional SNMP | Power management Support SNMP management and network management |
safety standards | |
safety regulations |
IEC/EN 60950-1; IEC/EN 62040-1 |
electromagnetic specification |
IEC/EN 62040-2 Categ0ry C3 |