LIRUISI Uninterrupted Power Supply Unit HP 60KVA 3 Phase Online UPS
Product Introduction:
An uninterruptible power supply (UPS) is a device used to protect electronic equipment from power failures such as power failures, voltage runouts, transient power failures, etc. It supplies electronic devices by converting DC power (such as batteries) into AC power to provide power supply in the event of a power outage or power failure to guarantee the normal operation of equipment and continuous operation of data. The UPS can power the device in seconds to tens of minutes to back up files, save data, or shut down. In some occasions where long-term continuous power supply is required, such as UPS can also be used with generators to ensure the stable power supply of equipment.
Product Features:
The output has an isolation transformer to ensure that the load and the utility grid are fully isolated.
Product parameters:
HP10KVA-HP400KVA [Power frequency tower three-in, three-out UPS system] | |
Model | HP60KVA |
Nominal capacity (KW) | 48 |
Single-phase input maximum current (A) | 114 |
Working method and principle | In-line power supply, static bypass switch (non-stop switching), double conversion technology, the output power supply is completely isolated |
Input power factor | 0.8/0.9 (12 pulses)/0.95 (with active filter) |
Phase number | Three-phase + N + G |
Nominal voltage | 380VAC±25% |
Nominal frequency | 50HZ±10%,60HZ±10% |
voltage harmonic distortion | <5% |
soft start | 0~100% 5 sec |
HP10KVA-HP400KVA [Power frequency tower three-in, three-out UPS system] battery | |
Maximum discharge current (A) | 169 |
Number of batteries per group | 12V type 32 sections or 2V type 192 sections |
Nominal battery voltage | 384VDC(348V-384V);160~400KVA:384/396VDC |
float voltage | 432VDC |
charging current | 6~ 30A (adjustable) |
HP10KVA-HP400KVA [Power frequency tower three-in, three-out UPS system] bypass | |
Phase number | Three-phase + N + G |
Nominal voltage | 380VAC±15% |
Nominal frequency | 50HZ±5%;60HZ±5% |
Transition time | 0ms |
HP10KVA-HP400KVA [Power frequency tower three-in, three-out UPS system] overall system | |
Communication interface | RS232, RS485, Dry Contacts, Smart Slots |
Operating temperature | 0~40℃ |
Relative humidity (non-condensing) | 0%~90% |
Operating height (max) | < 1000 meters (1% decrease in power for each additional 100 meters, up to 4000 meters) |
Cooling method | forced ventilation |
Protection class | IP20 |
Box color | White or black |
Easy to maintain | Front/top/side |