Install Quickly Automatic Control Gas Fired Oil Fired Steam Boiler For Heating
The fuel gas vapor boiler is a three-return fire tube boiler with internal combustion. Using the low-level symmetrical arrangement furnace bile wet back structure, high temperature smoke in turn washed the second and third return pipe, and then from the back smoke chamber through the chimney into the atmosphere. The boiler is equipped with the front and rear smoke box lid of the activity, which makes the boiler easy to carry out. Boiler configuration technology has good performance of industrial burners, the use of automatic proportional combustion, automatic water distribution, program start-stop, automatic operation and other advanced technology, and has high and low water level alarm and very low water level, ultra-high vapor pressure, fire and other automatic protection functions.
Central heating boiler room
Part of product parameter
WNS2-1.25-YQ
NO; | Name | Unit | Number | Description |
1 | Rated evaporation | t/h | 2 | |
2 | Rated working power | Mpa | 1.25 | |
3 | Rated outlet ℃ | ℃ | 193 | |
4 | Design efficiency | % | 92.6(Oil) | |
5 | Boiler heat efficiency | % | More than 98% | Be added economizer |
6 | Design fuels | / | Light oil,Gas | |
7 | Fuels LHV | MJ/kg | 42.917(Oil) | |
MJ/Nm3 | 35.438(Gas) | |||
8 | Consumption of fuels | kg/h | 137.9(Oil) | |
Nm³/h | 167.325(Gas) | Be added economizer | ||
9 | Radiation heating area | m² | 8.527 | |
Convection heating area | m² | 41.838 | ||
GGH heating area | m² | 23.195 | ||
10 | Fume temperature | ℃ | 137.863(Oil) | |
℃ | 134.28 (Gas) | |||
11 | Fume temperature | ℃ | 60-80 | Be added economizer |
12 | Excess air coefficient | / | 1.15 | |
13 | Volume | m3 | 5 | |
14 | Bulk weight | kg | 9700 | |
15 | Bulk size | mm | 4531×2150×2544 | |
16 | Chimney | mm | Φ500×10000 | |
17 | Total power consumption | KW | Oil:13,Gas:11 | |
18 | Combustion model | / | Micro positive pressure | Chamber combustion |
19 | Boiler structure feature(Three-pass structure) | Horizontal-type chamber combustion | ||
20 | Control way | Full automation/Manual | ||
21 | Ignition way | High-tension/Electrode |
WNS4-1.25-YQ
NO; | Name | Unit | Number | Description |
1 | Rated evaporation | t/h | 4 | |
2 | Rated working power | Mpa | 1.25 | |
3 | Rated outlet ℃ | ℃ | 194 | |
4 | Design efficiency | % | 92.06(Oil) | |
5 | Boiler heat efficiency | % | More than 98% | Be added economizer |
6 | Design fuels | / | Light oil,Gas | |
7 | Fuels LHV | MJ/kg | 42.917(Oil) | |
MJ/Nm3 | 35.438(Gas) | |||
8 | Consumption of fuels | kg/h | 275.8(Oil) | |
Nm³/h | 334.65(Gas) | Be added economizer | ||
9 | Radiation heating area | m² | 10.955 | |
Convection heating area | m² | 83.887 | ||
GGH heating area | m² | 21.488 | ||
10 | Fume temperature | ℃ | 140.6(Oil) | |
℃ | 137.75 (Gas) | |||
11 | Fume temperature | ℃ | 60-80 | Be added economizer |
12 | Excess air coefficient | / | 1.15 | |
13 | Volume | m3 | 5 | |
14 | Bulk weight | kg | 8000 | |
15 | Bulk size | mm | 4300×1900×2400 | |
16 | Chimney | mm | Φ400×10000 | |
17 | Combustion model | / | Micro positive pressure | Chamber combustion |
18 | Boiler structure feature(Three-pass structure) | Horizontal-type chamber combustion | ||
19 | Control way | Full automation/Manual | ||
20 | Ignition way | High-tension/Electrode |
Etc
Our Service
Pre-sale service:
We help customer choose the best boiler model according to different requirements of various industry. Before delivery we will provide foundation drawing, layout drawing, boiler room layout, etc.
In-sale service:
We keep 24 hours online and keep close contacts during the production process to ensure on time delivery with perfect finished product.
After-sale service:
1. provide full range of original spare parts.
2. Engineers abroad installation and commissioning service is available.
3. Our engineers will held a training for boiler workers to ensure the safe operation.
4. Free maintenance and repair for one year and lifelong service.