Specifications
Brand Name :
ESTEL
Model Number :
HE06-40SEH/01
Certification :
ISO9001, CE, 3C, FCC, TLC
Place of Origin :
Shenzhen, China (Mainland)
MOQ :
1
Price :
negotiation
Payment Terms :
L/C, D/A, D/P, T/T, Western Union
Supply Ability :
12,000 sets per month
Delivery Time :
7-10 working days
Packaging Details :
carton + foam + wooden case
Cooling Method :
heat pipe, passive cooling
Protection Level :
IP55
Cover Material :
galvanized steel
Rated Input Power :
57W
Rated Input Current :
1.2A
Description

400W Mixed Liquid Air To Air Heat Exchanger For Outdoor Telecom Enclosure

Quick Details:

Place of Origin: Shenzhen, China (Mainland) Rated Heat Exchange Capacity: 40W/K
Brand Name: ESTEL Rated Heating Capacity:300/500W (optional)
Model: HE06-40SEH/01 Rated Input Voltage: DC48V
Product Name: Outdoor Cabinet Heat Exchanger Rated Input Current: 1.2A
Certification: ISO9001, CE, 3C, FCC, TLC Rated Input Power: 57W
Cover Material: galvanized steel Working Temperature: -20°C ~ +55°C
Color: gray MTBF: 70000 hours
Protection Level: IP55 Noise: ≤62dB
Installation Mode: door mounted, side mounted Dimension W×D×H: 347×153.5×538mm
Support OEM Cooling Method: heat pipe, passive cooling

Payment & Shipping Terms:

Minimum Order Quantity: 1 set
Price: negotiation
Payment Terms: L/C, D/A, D/P, T/T, Western Union
Supply Ability: 12,000 sets per month
Delivery Time: 7-10 working days
Packaging Details: carton + foam + wooden case

1. Specifications

(1) Technical Parameters

Model No. HE06-40SEH/01
Environmental Performance working environmental temperature -20°C ~ 55°C
storage working temperature -50°C ~ 70°C
working humidity ≤95%
Thermal Performance rated heat exchange capacity 40W/K
heating input power 300/500W optional

Electrical Performance

rated input current 1.2A
rated input power 57W
input voltage DC48V
Safety MTBF 70000 hours
Noise ≤62dB

Dimension Diagram: 347×153.5×538 mm (W×D×H)

400W Mixed Liquid Air To Air Heat Exchanger For Outdoor Telecom Enclosure

2. Description

The HE06-40SEH/01 Mixed Working Fluid Heat Exchanger is a full automation temperature control product. It uses intelligent controller to control the whole system of the heat exchanger. According to the variation of environment temperature, the intelligent controller can automatically detect, operate and record the whole system’s operating time, power consumption, event and historical data. It can store 100 event records and 1280 historical data records, and can enquire 256 days’ daily record information.

3. Application

The product is widely applied in outdoor telecom cabinet, UPS cabinet, outdoor base station cabinet, outdoor advertising LED displayer, bank ATM etc.

4. Features

  • Strong adaptability
  • High intelligence
  • High precision
  • High reliability
  • The heat exchange capacity can be set according to need
  • Low noise
  • Low energy consumption
  • Wide input voltage range: DC36 - 65V
  • With dry contact alarm output
  • Dust proof and water proof

5. System Principle Diagram

400W Mixed Liquid Air To Air Heat Exchanger For Outdoor Telecom Enclosure

6. Electrical Wiring Diagram

400W Mixed Liquid Air To Air Heat Exchanger For Outdoor Telecom Enclosure

Diagram 3: Wiring Diagram

Wiring Ports:

0V -48V: power supply input (voltage input: DC36 - 65V)

A+ B- SGND: RS485 communication interface

AL1 AL2: general alarm output

F+ F- : auxiliary direct ventilation control output (output voltage: DC48V)

7. Wiring Diagram

400W Mixed Liquid Air To Air Heat Exchanger For Outdoor Telecom Enclosure

J1: button;

J2: inner temperature sensor input: 1—5V, 2—inT, 3—GND;

J3: outer temperature sensor input: 1—5V, 2—outT, 3—GND;

J4: Prog programming port;

JD1: DC48V input, 1—48V+, 2—48V-;

JD2: heater power supply: 1—0V (-), 2—48V (+);

JD3: 1, 2 - direct ventilation output, 1—48V (+), 2—0V (-);

3, 4 - system alarm output (dry contact, close alarm);

5, 6 - temperature alarm output (dry contact, close alarm);

JD4: fans control port:

fans and water pump power supply ( water pump uses 2 wire +-): 1 — 48V+, 6 — 0V-;

inner fans control: 2 — Y1 (control output), 3 — W1 (feedback input);

outer fans control: 4 — Y2 (control output), 5 — W2 (feedback input);

JD5: RS485 communication port: 1 — B-, 2 — A+, 3 — SGND.

8. Packing and Shipping


400W Mixed Liquid Air To Air Heat Exchanger For Outdoor Telecom Enclosure

9. Our Delivery Agent

The goods can be shipped by sea, by air, by courier, by land, by train, etc. Besides the following delivery agent, we can also look for the delivery agent with the best price in china if you need us to do for you.

10. Our Contact Information

Mobile Phone: 0086-13752765943

Telephone: 0086-0755 66600941

Email: info@estel.com.cn

lxf.estel@hotmail.com
Skype: fiona.liang10

Send your message to this supplier
Send Now

400W Mixed Liquid Air To Air Heat Exchanger For Outdoor Telecom Enclosure

Ask Latest Price
Brand Name :
ESTEL
Model Number :
HE06-40SEH/01
Certification :
ISO9001, CE, 3C, FCC, TLC
Place of Origin :
Shenzhen, China (Mainland)
MOQ :
1
Price :
negotiation
Contact Supplier
400W Mixed Liquid Air To Air Heat Exchanger For Outdoor Telecom Enclosure
400W Mixed Liquid Air To Air Heat Exchanger For Outdoor Telecom Enclosure
400W Mixed Liquid Air To Air Heat Exchanger For Outdoor Telecom Enclosure
400W Mixed Liquid Air To Air Heat Exchanger For Outdoor Telecom Enclosure
400W Mixed Liquid Air To Air Heat Exchanger For Outdoor Telecom Enclosure
400W Mixed Liquid Air To Air Heat Exchanger For Outdoor Telecom Enclosure

Tianjin Estel Electronic Science and Technology Co.,Ltd

Verified Supplier
10 Years
guangdong, shenzhen
Since 2002
Business Type :
Manufacturer, Distributor/Wholesaler, Exporter
Total Annual :
15 Million-20 Million
Employee Number :
101~200
Certification Level :
Verified Supplier
Contact Supplier
Submit Requirement