Specifications
Brand Name :
ESTEL
Model Number :
GPDA1000VA-F
Certification :
ISO9001, CE, 3C, FCC, TLC, IP55
Place of Origin :
Shenzhen, China (Mainland)
MOQ :
1 set
Price :
Negotiation
Payment Terms :
T/T, L/C,D/A, Western Union, Paypal, etc
Supply Ability :
2,000 sets per month
Delivery Time :
15-20 working days
Packaging Details :
Wooden case
Rated Capacity :
1000VA
Voltage input :
40 - 60 Vdc
Output voltage :
220VAC
Operating temperature :
-40ºC to +75 ºC
Application :
telecom
Type :
Telecom Rectifier
Description

AC Bypass input RS485 Communication Function DC / AC 1000VA Sine Wave Inverter Flush Mounting Power Supply

1. Product Description

GPDA1000VA-F is one kind of two outputs, with AC bypass input, with 485 communication function DC / AC 1000VA sine wave inverter flush mounting power supply, the entire power supply using the latest circuit design, compact structure, reliable performance, high output efficiency. Entire power in strict accordance with safety requirements designed to meet the IT equipment safety standards.

2. Electrical Specifications

Input
Parameter Min. Typical Max. Unit Note
DC input DC operating voltage range 40 60 Vdc
Input rated voltage 48 Vdc
Input Rated Current 30 A Rated input, rated output
Power input Max Surge Current 45 A ≤ 150% of rated current
AC input AC operating voltage range 175 265 Vac
Input rated voltage 220 Vac
Input Rated Current 5 A

Export
Parameter Min. Typical Max. Unit Note
The inverter output Rated output voltage 220 Vac Enter the full voltage range
Rated output current 4.6 A
Output voltage accuracy ±5 % Enter the full voltage range
Rated output frequency 49 50 51 Hz
Rated Capacity 1000 VA
Rated output power 1000 W
Overall efficiency 85 % Rated operating conditions
Output power factor 0.8 Rated operating conditions
Dynamic transient recovery time 60 ms
Waveform Sine wave THD <3% (linear load)
Sine wave THD <8% (linear load)
Overload 105~ 125% for not less than 10 minutes to 125 to 150% for not less than 10 seconds.
Output current crest factor 3: 1
Output Two AC output
AC bypass output Output voltage range 175 265 Vac With the AC input voltage changes
Rated output voltage 220 Vac
Rated output current 5 A
Switch to mains inverter output time 10 ms Rated load
Mains to inverter output time 10 ms Rated load
Output Total output of the inverter, the inverter when an input under voltage, overvoltage, fan failure, over-temperature protection, switching to bypass output.

DC / AC 1000VA Sine Wave Inverter Flush Mounting Power Supply AC Bypass Input

Protection
Parameter Min. Typical Max. Unit Note
Inverter part DC input voltage protection point 36 Vdc Enter under voltage protection, the inverter output bypass switch.
DC input voltage recovery point 40 Vdc Achieve recovery value, one minute to restore the inverter output.
DC input voltage recovery hysteresis 2 Vdc
DC input voltage protection point 66 Vdc Enter overvoltage protection, the inverter switch to bypass the output.
DC input overvoltage recovery point 60 Vdc Achieve recovery value, one minute to restore the inverter output.
DC input overvoltage recovery hysteresis 2 Vdc
Input over current protection Power supply with input over current protection, can not be automatically restored.
Over Temperature Protection Power supply with over-temperature protection. When inside the main heat sink temperature is too high, over-temperature protection point reached, the inverter output bypass switch, temperature hysteresis of 10℃ or so.
Anti-reverse protection Power supply with input anti-reverse protection. When reversed, the power does not work, and no damage.
Short circuit protection Power supply with short circuit protection. When the power fails short intervals of one minute start time, 6 minutes lift failure, can be recovered. Long-short, the power shutdown, the short is removed, you can manually re-boot after work.
Output over current protection Power supply with over current protection. Detect over current, output power is turned off, every one minute start time, when the load back to the ratings, self-recovery. Long-term overload, power off, you can manually reboot after work.
Alarm (buzzer alarm) DC input error, overload, short circuit, inverter fault, the buzzer alarm.
AC bypass section Input over current protection Bypass input section having an input over current protection function (≥ 10 A), non-self-recovery. The need to manually replace the fuse before working again.

Environment
Parameter Min. Typical Max. Unit Note
Operating ambient temperature - 20 +5 5 ° C
Inverter temperature storage environment - 25 +70 ° C
Relative humidity 0 95 % Relative humidity, dew does not pour
Altitude 15 00 m Meet derating requirementsGB3859.2-93
Cooling Natural air. With the power of wind turbines internal temperature rises enhanced, cold heat.
Work Environment No conductive dust explosion, corrosion and destruction of gases and vapors, no severe vibration and shock

5. Product Dimensions

DC / AC 1000VA Sine Wave Inverter Flush Mounting Power Supply AC Bypass Input

6. Product Pictures

DC / AC 1000VA Sine Wave Inverter Flush Mounting Power Supply AC Bypass Input

Send your message to this supplier
Send Now

DC / AC 1000VA Sine Wave Inverter Flush Mounting Power Supply AC Bypass Input

Ask Latest Price
Brand Name :
ESTEL
Model Number :
GPDA1000VA-F
Certification :
ISO9001, CE, 3C, FCC, TLC, IP55
Place of Origin :
Shenzhen, China (Mainland)
MOQ :
1 set
Price :
Negotiation
Contact Supplier
DC / AC 1000VA Sine Wave Inverter Flush Mounting Power Supply AC Bypass Input

Tianjin Estel Electronic Science and Technology Co.,Ltd

Verified Supplier
10 Years
guangdong, shenzhen
Since 2002
Business Type :
Manufacturer, Distributor/Wholesaler, Exporter
Total Annual :
15 Million-20 Million
Employee Number :
101~200
Certification Level :
Verified Supplier
Contact Supplier
Submit Requirement