Stainless Steel Air Conditioner Cooling Outdoor Telecom Cabinet Includes PDU , DDF
1.Technical Parameter
Item | Type | Technical Parameter |
Structure | Dimension | External Dimension: H×W×D 2000×750×700mm |
Layout | 1 compartment | |
Door | With one front door, and anti-theft three point lock for outdoor cabinet (support padlock) | |
Material | 304 Stainless Steel, single wall with insulation | |
Ingress Protection | IP55 | |
Temperature Control | Cooling | Air conditioner and fans |
Lighting | LED lamp | 48V LED lamp |
Temperature | Temperature | Working Temperature: -40°C ~ +55°C |
Storage Temperature: -50°C ~ + 70°C | ||
Transport Temperature: -50°C ~ +70°C | ||
Humidity | Relative Humidity | 5% ~ 100% |
Pressure | Air Pressure | 62kpa ~ 101kpa (similar to 0m ~ 5000m altitude) |
Radiation Intensity | Solar Radiation Intensity | 1120 ×(1±5%)W/m2 |
2.Configuration Table
No. | Item | Quantity | Unit | Specs |
1 | Outdoor Telecom Cabinet | 1 | Set | (1)External Dimension: H×W×D 2000×750×700mm (2)One compartment: including 19” rack (3)With one front door , and anti-theft three point lock for outdoor cabinet (support padlock) (4) Material: 304 Stainless Steel, single wall with insulation |
2 | Air Conditioner | 1 | Set | Cooling Capacity: 2000W; Power Supply: DC48V |
3 | Fan | 2 | PC | DC48V |
4 | LED Lamp Sensor | 1 | PC | Used for controlling LED lamp on/off |
5 | LED Lamp | 1 | PC | DC48V,used for illumination in the cabinet |
6 | DDF | 1 | Set | (1)Model:MPX108-SM16 (2) Capacity: 16 system (3) Size: H×W×D 110×485×95mm (4) Connection method: SIEMENS mode (5) Including cable and related accessories, cable head specifications: 75-2-1 |
7 | Package | 1 | Set | Wooden Case |
3. Cable Inlet
The cable entry points are situated behind the cabinet, 6 top and 4 bottom and easy upgradeable.
4. Grounding Protection
4.1 The cabinet includes grounding copper bar with anti-corrosion coating. There are enough screws for wiring connection terminals.
4.2 The metal part of the cabinet should be interconnected and be connected with grounding bar. Connection resistance between any two points is lower than 0.1Ω.
4.3 Protective earthing of other equipments inside the cabinet should be connected to the grounding bar.
5.Internal Pictures
There are one monitor and one PDU and one DDF installed on the 19 inch rack inside of the cabinet.
6. Cabinet Cooling
There is one 2000W air conditioner installed on the front door.
There are 2 fans installed on the front door.
7.Delivery Time
Generally it will take about 20 days to produce the cabinet.