220VAC Rectifier System Up To 3.48kW For Telecom Applications With RS485
220VAC Rectifier System Product Introduction
sub-rack power supply with 1U height compact design can meet critical application needs of fiber and microwave transmission, access device and switch. The system maximum power is 3.48KW, with AC/battery/load MCBs.
220VAC Rectifier System Key Feature
220VAC Rectifier System Product Applications
220VAC Rectifier System Specification
Category | ET4860-001 | |
System | Dimension(mm) | 441.0(W)*300.0(D)*1U(H) |
Weight | ≤10kg(without rectifier module) | |
Cooling mode | Natural cooling | |
Installation mode | Installed on 19-inch rack or inside the cabinet | |
IP Grade | IP20 | |
AC Distribution | Input mode | 220VAC |
Input capacity | 30A/3P terminal | |
Input frequency | 45~65Hz, rated value: 50Hz/60Hz | |
DC Distribution
| Output voltage | -43~-58VDC, rated value: -53.5VDC |
Maximum capacity | 3.48kW | |
Battery breaker | 1 x 50A/1P | |
Load breakers | 2×10A/1P, 2×40A/1P | |
Rectifier | Input voltage | 85VAC~300VAC, rated 220VAC |
Efficiency | ≥96% | |
Rated power | 1740W(176~300VAC) | |
Working temperature | -40℃~+75℃(fully output below 50℃) | |
Dimension | 106.5mm(W)×286mm(D)×41.5mm(1U/H) | |
Weight | ≤2kg | |
Cooling mode | Forced cooling with fan | |
Power factor | ≥0.99 | |
THD | ≤5% | |
Controller | Signal input | 4 AI(3 Battery temp., 1 ambient temp) ,7 DI(SPD, 6 common DI) |
Alarm output | 4 dry contact | |
Communication port | RS485, SNMP | |
Display mode | LCD | |
Environment
| Operating temperature | -40℃~+75℃(fully output below 50℃) |
Storage temperature | -40℃~+70℃ | |
Operating humidity | 5%~95%(non-condensing) | |
Altitude | 0~3000m(If the altitude is within the range of 2000m to 3000m, the maximum operating temperature decreases by 1℃ as the altitude increases by 200m.) |
Diagram
Product images:
Rectifier module:
Controller: