1. Application
This heat exchanger is mainly used for outdoor cabinet heat exchange. Also widely applied in small and medium sized telecom room, UPS room, outdoor base station room, outdoor advertising machine, bank ATM room etc.
2. Brief
Heat Pipe Heat Exchanger is a full automation temperature control product. It uses intelligent controller to control the whole system of the heat exchanger. According to the variation of environment temperature, the intelligent controller can automatically detect, operate and record the whole system’s operating time, power consumption, event and historical data. It can store 100 event records and 1280 historical data records, and can enquire 256 days’ daily record information.
Heat exchanger is mostly used for enclosed area cooling, HEX is designed especially for mounting in a cabinet. The unit uses ambient air for temperature regulation so it must have access to ambient. The internal temperature of the enclosure is cooled via effective utilization of the ambient air.
3. Technical Parameters
Model No. | HE06-80SEH/01 |
working environmental temperature | -20°C ~ 55°C |
storage working temperature | -40°C ~ 70°C |
working humidity | ≤95% |
rated heat exchange capacity | 80W/K |
rated heating capacity | 300/500W (optional) |
rated input current | 2.0A |
rated input power | 96W |
rated input voltage | DC48V |
Noise | 62dB |
4. Dimension Diagram:
430×176×700 mm (W×D×H)
Size | Model No. | A | B | C | D | E | F | G | H | I | J | K |
80W/K Heat Exchanger | HE06-80SEH/01 | 300 | 401 | 450 | 600 | 672 | 700 | 133 | 176 | 649 | 379 | 430 |
Wiring Ports:
0V -48V: power supply input (voltage input: DC36 - 65V)
A+ B- SGND: RS485 communication interface
AL1 AL2: general alarm output
F+ F- : auxiliary direct ventilation control output (output voltage: DC36 - 65V)
8. Picture of Heat Exchanger installed on the cabinet
9. Details
10. Packing