1. 30U Outdoor Power Cabinet Technical Parameters
No. | Item | Quantity | Unit | Specs |
1. | Outdoor Power Cabinet | 1 | Set | (1) External Dimension: W*D*H 900*900*2100mm |
2. | Air Conditioner | 1 | Set | Cooling capacity: 3000W, Power Supply: 48VDC |
3. | Auxiliary Direct Ventilation Fans | 2 | PC | 48VDC,install on the cabinet door |
4. | Rectifier System | 1 | SET | 48V 300A,support SNMP communication protocol |
5. | Water Sensor | 1 | PC | Optional |
6. | Smoke Sensor | 1 | PC | Optional |
7. | Temperature and Humidity Sensor | 1 | PC | Optional |
8. | Door Sensor | 1 | PC | Optional |
9. | LED Lamp | 1 | PC | 48VDC |
10. | Package | 1 | Set | Wooden Case |
2. Outdoor Enclosure Stainless Steel Cabinet Rectifier System Parameter
Category | ET483300-002 | |
System | Dimension(mm) | 482.0(W)*350.0(D)*5U(H) |
Weight | ≤25kg(without rectifier module) | |
Cooling mode | Natural cooling | |
Installation mode | Installed on 19-inch rack or inside the cabinet | |
IP Grade | IP20 | |
AC Distribution | Input Voltage | 380Vac,three phase |
Input capacity | 1*63A/4P | |
Input frequency | 45~65Hz, rated 50/60Hz | |
AC SPD | 20kA/40kA, 8/20μs | |
DC Distribution | Output voltage | -43~-58VDC,rated value:-53.5VDC |
Maximum capacity | 18kW(6*3000W rectifier module) | |
Battery connection | 2*125A/1P | |
Load breakers | LLVD:63A/1P×3+32A/1P×3+16A/1P×2 BLVD:32A/1P×2+16A/1P×3 | |
DC SPD | 10kA, 8/20μs | |
Rectifier module | Efficiency | ≥96%@340Vdc/ 53.5VDC rated load |
Rated power | 3000W(85~300Vdc ) | |
Working temperature | -40℃~+75℃(fully output below 50℃) | |
Dimension | 105.5mm(W)×286mm(D)×41.5mm(1U/H) | |
Cooling mode | Forced cooling with fan | |
Controller | Signal input | 4 AI(3 Battery temp., 1 ambient temp) ,6 DI(SPD, 6 common DI) |
Alarm output | 4 dry contact | |
Communication port | LAN/RS232/RS485 interface,LAN-SNMP,TCP/IP | |
Display mode | LCD | |
Environment | Operating temperature | -40℃~+65℃ |
Storage temperature | -40℃~+70℃ | |
Operating humidity | 0%~95%(non-condensing) | |
Altitude | 0~3000m(If the altitude is within the range of 2000m to 3000m, the maximum operating temperature decreases by 1℃ as the altitude increases by 200m.) |
3. ESTEL Outdoor Telecom Cabinet With Rectifier System Introduction:
The outdoor cabinet is widely used in telecom operators’ mobile telecommunication sites, outdoor small shelters, railway electrical control cabinets, electronic police, communication base stations, outdoor air detection stations, solar control cabinets,etc.
4. Intergrated Outdoor Power Cabinet Pictures
5. Outdoor Cabinet with Sensors Enclosure Instruction
For those who need more than just standard cabinet, this series can also offer a truly the security of customized solution with lots of available options, providing a climate-controlled environment for any electronic equipment, electrical load panels and cable entry solutions. It provides a secure,climate controlled environment for any electronic equipment.
This battery cabinet is 1750mm High and750mm Wide and 750mmDeep. This cabinet is the ultimate choice for outdoor racking requirements.
Standard | Description |
GB/T 17626.7-1998 | Electromagnetic compatibility |
GB4706.1 | Safety of household appliance and electrical appliance with similar use. |
GB4798.1 | Environmental conditions existing in the application for electric and electronic products - storage |
GB4798.2 | Environmental conditions existing in the application for electric and electronic products - transportation |
GB4798.3 | Environmental conditions existing in the application for electric and electronic products - usage |