Ambient temperature | 0-55 ° C: During operation, -25-75 ° C: During storage | ||
Relative humidity | 5 to 95% RH (no condensation) ・ ・ ・ ・ ・ ・ During operation | ||
Vibration resistant | When mounting the DIN rail | Frequency: 10-57Hz | One-sided amplitude: 0.035mm X, Y, Z 10 times in each direction (80 minutes in total) Judgment criteria are based on IEC 61131-2 |
Frequency: 57-150Hz | Acceleration: 4.9m / s 2 X, Y, Z 10 times in each direction (80 minutes in total) Judgment criteria are based on IEC 61131-2 | ||
At the time of direct mounting | Frequency: 10-57Hz | One-sided amplitude: 0.075mm X, Y, Z 10 times in each direction (80 minutes in total) Judgment criteria are based on IEC 61131-2 | |
Frequency: 57-150Hz | Acceleration: 9.8m / s 2 X, Y, Z 10 times in each direction (80 minutes in total) Judgment criteria are based on IEC 61131-2 | ||
Impact resistance | 147m / s 2 , action time 11ms, sine and cosine half-wave pulse 3 times in each direction of X, Y, Z Judgment criteria are based on IEC61131-2 | ||
Noise resistance | Based on a noise simulator with a noise voltage of 1,000 Vp-p, a noise width of 1 μs, a rise of 1 ns, and a period of 30 to 100 Hz. | ||
Withstand voltage | When conducting a withstand voltage test, use the following voltage between each terminal and the ground terminal of the basic unit. Between power supply terminal (AC power supply) and ground terminal: AC1.5kV 1 minute DC24V service power supply, and between input terminal (DC24V) and ground terminal: AC500V 1 minute Between output terminal (transistor) and ground terminal: AC500V 1 minute | ||
Insulation resistance | When conducting an insulation resistance test, use the following voltage between each terminal and the ground terminal of the basic unit. Between power supply terminal (AC power supply) and ground terminal: 5MΩ or more with DC500V insulation resistance tester DC24V service power supply, and between input terminal (DC24V) and ground terminal: 5MΩ or more with DC500V insulation resistance tester Output terminal (transistor) and ground terminal Between: 5MΩ or more with DC500V insulation resistance tester | ||
ground | Class D grounding (grounding resistance: 100Ω or less) <Common grounding with strong electric system is not possible> Grounding should be dedicated grounding or shared grounding. | ||
Usage atmosphere | No corrosive or flammable gas, no terrible conductive dust | ||
Altitude used | It cannot be used in an environment where the pressure is 2000 m or less and the atmospheric pressure is higher than the atmospheric pressure. It may break dow |