Number of inputs and outputs | Number of digital outputs: 2 |
Measuring range | |
Process connection | threaded connection G 1/4 |
Installation length EL [mm] | 50 |
Application
System | gold-plated contacts |
Measuring element | 1 x Pt 1000; (to DIN EN 60751, class A) |
Media | liquids and gases |
Medium temperature [°C] | -40...145 |
Pressure rating [bar] | 400 |
Electrical data
Operating voltage [V] | 9.6...32 DC; (cULus - Class 2 source required) |
Current consumption [mA] | < 30 |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | 0.5 |
Inputs / outputs
Number of inputs and outputs | Number of digital outputs: 2 |
Outputs
Total number of outputs | 2 |
Output signal | switching signal |
Electrical design | PNP |
Number of digital outputs | 2 |
Output function | complementary |
Max. voltage drop switching output DC [V] | 2 |
Permanent current rating of switching output DC [mA] | 500 |
Short-circuit protection | yes |
Type of short-circuit protection | yes (non-latching) |
Overload protection | yes |
Measuring/setting range
Measuring range | |
Set point SP | |
Reset point rP | |
Accuracy / deviations
Temperature drift per 10 K [K] | 0.1 **) |
Repeatability [K] | ± 0,1 |
Setting accuracy [K] | ± 3 |
Reaction times
Dynamic response T05 / T09 [s] | 1 / 3; (according to DIN EN 60751) |
Software / programming
Adjustment of the switch point | setting rings |
Operating conditions
Ambient temperature [°C] | -40...80 |
Note on ambient temperature | at medium temperature: < 80 °C | -40...50 °C | at medium temperature: < 145 °C | |
Storage temperature [°C] | -40...100 |
Protection | IP 67 |
Tests / approvals
EMC | DIN EN 61000-4-2 ESD | 4 kV CD / 8 kV AD | EN 61000-4-3 HF radiated | 10 V/m | DIN EN 61000-4-4 Burst | 2 kV | EN 61000-4-6 HF conducted | 10 V | |
Shock resistance | DIN IEC 68-2-27 | 50 g (11 ms) | |
Vibration resistance | DIN EN 60068-2-6 | 20 g (10...2000 Hz) | |
MTTF [years] | 643.1 |
UL approval | |
Mechanical data
Weight [g] | 104.5 |
Material | stainless steel (1.4404 / 316L); PC; PBT; FKM |
Materials (wetted parts) | stainless steel (1.4404 / 316L); FKM |
Tightening torque [Nm] | 35 |
Process connection | threaded connection G 1/4 |
Probe diameter [mm] | 6 |
Installation length EL [mm] | 50 |
Displays / operating elements
Display | Power | LED, green | Switching status | LED, yellow | |
Remarks
Remarks | **) In case of deviation from the reference condition 25 °C | The values for accuracy apply to flowing water. | |
Pack quantity | 1 pcs. |
Electrical connection
Connection | Connector: 1 x M12; coding: A; Contacts: gold-plated |