Product Description
Material number:
X20CM0985
Description:
Energy measurement for 120 to 480 VAC
Simultaneous measurement of 2 AC mains networks plus 2 additional voltages
For multifunctional measurement tasks
Intelligent mains synchronization unit
The module has a compact size and combines a power measurement module that has special features with a synchronization unit that is able to meet all demands.
The measurement unit's 3 current inputs are suitable for both X: 1 A and X: 5 A current transformers. Overcurrent resistance and the high resolution of the measurement unit round off its features. For the voltage inputs, the value range can be configured between 480 VAC and 120 VAC.
The area of use includes 4-wire AC networks with a phase voltage up to 480 VAC and 3-wire systems, whereas L2 can be grounded (V-connection). The module can also handle Aron measuring circuits.
The resulting measured values include the pure phase current; line-to-line voltage or phase voltage; the effective, reactive and apparent power parts; the mains frequency; the power factor and much more. In addition, peak values and energy meters are stored on the module in nonvolatile memory. Depending on the configuration, it is also possible to use a digital output as a pulse encoder for an external energy meter.
The synchronization unit doesn't just take the phasing and phase voltage into consideration; integrated intelligence also monitors the rate of change and other parameters, allowing them to influence when the synchronization output is switched. It is also possible to monitor a generator using a large number of additional conditions. A total of 4 voltage inputs provide substantial overall flexibility.
Monitoring functions expand the features of the module. Dependent overcurrent monitoring is included, which utilizes the thermal capacity of the motor/generator to allow short overloads while still providing full protection. The dependent, delayed imbalanced load monitoring used to protect three-phase generator and three-phase networks from imbalanced load can be adapted to the characteristics of different generator types using parameters while taking their special thermal time constants into account.
Product Information
Short description
I/O module | X20 energy measurement and synchronization module |
General information
B&R ID code | 0x2433 |
Status indicators | Channel status, operating state, module status |
Diagnostics |
|
Module run/error | Yes, using LED status indicator and software |
Analog inputs | Yes, using LED status indicator (measurement range of analog inputs) |
Digital outputs | Yes, using LED status indicator and software |
Overvoltage category | ll |
Power consumption |
|
Bus | 1.4 W |
Internal I/O | 4 W |
Additional power dissipation caused by actuators (resistive) [W] | - |
Certifications |
|
CE | Yes |
UKCA | Yes |
ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc |
UL | cULus E115267 |
HazLoc | cCSAus 244665 |
KC | Yes |
Digital outputs
Quantity | 5 |
Variant | Current-sourcing FET |
Nominal voltage | 24 VDC |
Switching voltage | 24 VDC -15% / +20% |
Nominal output current | 0.1 A |
Total nominal current | 0.5 A |
Connection type | 1-wire connections |
Output circuit | Source |
Output protection | Thermal shutdown in the event of overcurrent or short circuit |
Diagnostic status | Output monitoring with 10 ms delay |
Leakage current when the output is switched off | 5 μA |
Residual voltage | <0.3 V at 0.1 A nominal current |
Peak short-circuit current | <2 A |
Switch-on in the event of overload shutdown or short-circuit shutdown | Approx. 10 ms, depends on the module temperature |
Switching delay |
|
0 → 1 | <300 μs |
1 → 0 | <300 μs |
Switching frequency |
|
Resistive load | Max. 100 Hz |
Insulation voltage between channel and bus | 500 Veff |
Relay outputs
Quantity | 1 |
Variant | Relay / Changeover contact |
Nominal voltage | 30 VDC / 240 VAC |
Rated frequency | DC / 45 to 63 Hz |
Switching capacity |
|
Min. | 10 mA / 5 VDC |
Max. | 30 W / 240 VAC |
Nominal output current | 1 A at 30 VDC / 1 A at 240 VAC |
Actuator power supply | External |
Switching voltage | Max. 60 VDC / 250 VAC |
Switching delay |
|
0 → 1 | ≤10 ms |
1 → 0 | ≤10 ms |
Service life |
|
Mechanical | Min. 10 x 106ops. |
Electrical | Min. 60 x 103ops. (NC) at 1 A |
Contact resistance | Max. 100 mΩ |
Protective circuit |
|
Internal | None |
External | None |
DC | Inverse diode, RC combination or VDR |
AC | RC combination or VDR |
Insulation voltage |
|
Channel - Channel | 1000 VAC / 1 min |
Channel - Bus | 4000 VAC / 1 min |
Analog input voltage
Channels | 8 |
Input | 120 VAC / 480 VAC |
Input type | Single-ended |
Digital converter resolution | ±15-bit |
Conversion time |
|
50 Hz | 20 ms |
60 Hz | 16.67 ms |
Permissible input signal | Max. 132 VAC / 528 VAC |
Output format |
|
±120 VAC | 1 LSB = 0x0001 = 5.707 mV |
±480 VAC | 1 LSB = 0x0001 = 22.787 mV |
Output of digital value during overload |
|
Overshoot | 0x7FFF |
Undershoot | 0x8001 |
Conversion method | SAR |
Input filter |
|
Cutoff frequency | 10 kHz |
Slope | 60 dB |
Maximum gain drift | 0.02% per °C |
Maximum offset drift | 0.003% per °C |
Crosstalk between channels | -70 dB |
Nonlinearity | ≤0.5% at 45 to 65 Hz |
Protection against electric shock | Protective impedance per EN 61131-2 |
Test voltage between channel and bus (type test) | 3700 Veff |
Output format | INT |
Input impedance in signal range | Approx. 3 MΩ |
Max. error at 25°C |
|
Gain | 0.09% |
Offset | 0.03% |
Input protection | Overvoltage protection |
Analog input current
Channels | 3 |
Input | 1 A / 5 A AC |
Input type | Isolated current transformer according to the compensation principle with a magnetic sensor, for connecting an external transformer |
Digital converter resolution | ±15-bit |
Conversion time |
|
50 Hz | 20 ms |
60 Hz | 16.67 ms |
Permissible input signal | Max. 1.5 A / 7.7 A |
Output format |
|
±1 A | 1 LSB = 0x0001 = 189.903 μA |
±5 A | 1 LSB = 0x0001 = 949.513 μA |
Output of digital value during overload |
|
Overshoot | 0x7FFF |
Undershoot | 0x8001 |
Conversion method | SAR |
Input filter |
|
Cutoff frequency | 10 kHz |
Slope | 60 dB |
Maximum gain drift | 0.07% per °C |
Maximum offset drift | 0.003% per °C |
Crosstalk between channels | -70 dB |
Nonlinearity | ≤0.5% at 45 to 65 Hz |
Insulation voltage between channel and bus | 500 Veff |
Output format | INT |
Max. error at 25°C |
|
Gain | 0.2% |
Offset | 0.05% |
Thermal overcurrent | 15 x INom for 0.2 s |
Monitored overcurrent | 4 x INom |
Input impedance |
|
Measurement range 1 A | Max. 30 mΩ |
Measurement range 5 A | Max. 10 mΩ |
Electrical properties
Electrical isolation | Bus isolated from I/O power supply and digital inputs and outputs
Digital inputs and outputs isolated from each other |
Operating conditions
Mounting orientation |
|
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level |
|
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature |
|
Operation |
|
Horizontal mounting orientation | 0 to 60°C |
Vertical mounting orientation | 0 to 50°C |
Derating | See section "Derating". |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity |
|
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Mechanical properties
Note | Order 2x terminal block X20TB12 separately. |
Pitch | 87.5+0.2mm |
Product Photo
More Products
X20PS9600 | X20SO6300 | X20DC4395 |
X20CP0483 | X20SLX210 | X20BT9100 |
X20CP1483 | X20DI4371 | X20DI9371 |
x20cp1586 | X20BM05 | X20AT6402 |
X20CP1583 | X20BC0083 | X20AI4622 |
X20CP3584 | X20BC8083 | x20at4222 |
X20CP3583 | X20BB80 | x20bt9400 |
X20CP1585 | X20BM11 | X20AT2222 |
X20CP1584 | X20TB12 | X20AO4622 |
X20CP1684 | X20IF1072 | X20DO9322 |
X20CP1382 | X20DO6322 | X20IF1030 |
X20AI1744 | X20DC2395 | X20IF1082-2 |
X20DI6371 | X20BM15 | X20IF371 |
X20DOF322 | X20DO4332 | X20CM4810 |
X20DS4389 | X20DO4322 | X20AI83211 |
X20PS2100 | X20MM2436 | X20DOF322 |
X20PS9400 | X20DO8332 | X20PS3330 |
X20CS1030 | X20DC11A6 | X20BM01 |
X20CS1020 | X20CM8281 | X20SI9100 |
X20ATC402 | X20BR9300 | X20SI4100 |
Cooperative Brand
(DCS)
ABB / TRICONEX / FOXBORO/ I/A / HONEYWELL / TDC2000/3000 / YOKOGAWA / BENTLY NEVADA
(PLC)
B&R / ALLEN BRADLEY / BECKHOFF / HONEYWELL / OMRON / SIEMENS
(SENSOR)
IFM / SICK/ P+F/ WENGLOR / BAUMER / LEUZE / HOLLY/ SYSHOKUYO / EUCHNER
(CONNECTOR)
HARTING / PHOENIX CONTACT/ WEIDMUELLER
(VALVE)
SMC / FESTO / +GF+.......
(INSTRUMENT)
+GF+ /E+H / HITACHI / ROSEMOUNT
Why Choose Us
Xiamen ZhiCheng Automation Technology Co., Ltd it is a leading global supplier of control system components. We specialize in control systems and drives. With many years of experience in the industrial sector, we consistently deliver the highest quality of spare parts. We have tens of thousands of spare partsand spare parts warehouse . Products and services to serve for installing of users control system,Distributed control systems, programmable controllers, panel controller and drive!
We major in DCS system,Sensor,PLC,Connector,Valve, and Instrument,MAGNETRON,RO Membrane. With many years of experience in the industrial sector, we consistently deliver the highest quality of spare parts.which make sure that all this jobs are perfectly. If you have any further questions, please don't hesitate to contact us.
How To Contact Me