Application | ||||||||||||||
Measuring element | ceramic-capacitive pressure measuring | cell | ||||||||||||
Media | group 2 fluids according to the Pressure Equipment Directive (PED) | |||||||||||||
Conditionally suitable for | group 1 fluids on request | |||||||||||||
Medium temperature [°C] | -25...80 | |||||||||||||
Pressure rating | 75 bar | 1087 psi | 7.5 MPa | |||||||||||
Min. bursting pressure | 150 bar | 2175 psi | 15 MPa | |||||||||||
Vacuum resistance | [mbar] | -1000 | ||||||||||||
Type of pressure | relative pressure | |||||||||||||
Electrical data | ||||||||||||||
Operating voltage [V] | 18...30 DC; (according to EN 50178 SELV/PELV) | |||||||||||||
Current consumption | [mA] | < 35 | ||||||||||||
Min. insulation resistance [MΩ] | 100; (500 V DC) | |||||||||||||
Protection class | III | |||||||||||||
Reverse polarity protection | yes | |||||||||||||
Power-on delay time | [s] | 0.3 | ||||||||||||
Integrated watchdog | yes | |||||||||||||
Inputs / outputs | ||||||||||||||
Number of inputs and outputs | Number of digital outputs: 1; Number of analog outputs: 1 | |||||||||||||
ifmefector, inc. • 1100 Atwater Drive • Malvern • PA 19355 — We reserve the right to make technical alterations without prior notice. — EN-US — PN3594-01 — 24.05.2016 — | ||||||||||||||
PN3594 | ||||||||||||||
Pressure sensor with display | ||||||||||||||
PN-010-REG14-MFRKG/US/ /V | ||||||||||||||
Outputs | ||||||||||||||
Total number of outputs | 2 | |||||||||||||
Output signal | switching signal; analog signal; IO-Link; (configurable) | |||||||||||||
Electrical design | PNP | |||||||||||||
Number of digital outputs | 1 | |||||||||||||
Output function | normally open / closed; (configurable) | |||||||||||||
Max. voltage drop switching output DC | [V] | 2.5 | ||||||||||||
Permanent current rating of switching output DC | [mA] | 150; (200 (...60 °C) 250 (...40 °C)) | ||||||||||||
Switching frequency DC | [Hz] | < 170 | ||||||||||||
Number of analog outputs | 1 | |||||||||||||
Analog current output | [mA] | 4...20; (0 bar = 4 mA; 10 bar = 20 mA) | ||||||||||||
Max. load | [Ω] | 500 | ||||||||||||
Analog voltage output | [V] | 0...10; (0 bar = 0 V; 10 bar = 10 V) | ||||||||||||
Min. load resistance | [Ω] | 2000 | ||||||||||||
Short-circuit protection | yes | |||||||||||||
Type of short-circuit protection | yes (non-latching) | |||||||||||||
Overload | protection | yes | ||||||||||||
Measuring/setting range | ||||||||||||||
Measuring range | -1...10 bar | -14.5...145 psi | -0.1...1 MPa | |||||||||||
Set point SP | -0.9...10 bar | -13.5...145 psi | -0.09...1 MPa | |||||||||||
Reset point rP | -0.95...9.95 bar | -14...144.5 psi | > -0.095 MPa | |||||||||||
Insteps of | 0.05 bar | 0.5 psi | 0.005 MPa | |||||||||||
Accuracy / deviations | ||||||||||||||
Switch point accuracy | < ± 0,5 | |||||||||||||
[% of the span] | ||||||||||||||
Repeatability | [% of the span] | < ± 0,1; (with temperature fluctuations < 10 K) | ||||||||||||
Characteristics deviation [% of the span] | < ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting) | |||||||||||||
Hysteresis deviation [% of the span] | < ± 0,25 | |||||||||||||
Long-term stability [% of the span] | < ± 0,05; (per 6 months) | |||||||||||||
Temperature coefficient zero point [% of the span / 10 K] | < ± 0,2; (-0...80 °C) | |||||||||||||
Temperature coefficient span [% of the span / 10 K] | < ± 0,2; (-0...80 °C) | |||||||||||||
ifmefector, inc. • 1100 Atwater Drive • Malvern • PA 19355 — We reserve the right to make technical alterations without prior notice. — EN-US — PN3594-01 — 24.05.2016 — | ||||||||||||||
PN3594 | ||||||||||||||
Pressure sensor with display | ||||||||||||||
PN-010-REG14-MFRKG/US/ /V | ||||||||||||||
Reaction times | ||||||||||||||
Response time | [ms] | < 3 | ||||||||||||
Delay time programmable dS, dr | [s] | 0...50 | ||||||||||||
Damping for the switching output dAP | [s] | 0...4 | ||||||||||||
Damping for the analog output dAA | [s] | 0...4 | ||||||||||||
Max. response time analog output | [ms] | 3 | ||||||||||||
Software / programming | ||||||||||||||
Parameter setting options | hysteresis / window; normally open / closed; switch-on/ switch-off delay; Damping; Display unit; current/voltage output | |||||||||||||
Interfaces | ||||||||||||||
Communication interface | IO-Link | |||||||||||||
Transmission type | COM2 | |||||||||||||
IO-Link revision | 1.1 | |||||||||||||
SDCI standard | IEC 61131-9 | |||||||||||||
IO-Link device ID | 431 d / 00 01 afh | |||||||||||||
Profiles | Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis | |||||||||||||
SIO mode | yes | |||||||||||||
Required master port class | A | |||||||||||||
Process data analogue | 1 | |||||||||||||
Process data binary | 1 | |||||||||||||
Min. process cycle time [ms] | 2.3 | |||||||||||||
Operating conditions | ||||||||||||||
Ambient temperature [°C] | -25...80 | |||||||||||||
Storage temperature Protection | [°C] | -40...100 IP 65; IP 67 | ||||||||||||
Tests / approvals | ||||||||||||||
EMC | DIN EN 61000-6-2 | |||||||||||||
DIN EN 61000-6-3 | ||||||||||||||
Shock resistance | DIN EN 60068-2-27 | 50 g (11 ms) | ||||||||||||
Vibration resistance | DIN EN 60068-2-6 | 20 g (10...2000 Hz) | ||||||||||||
MTTF [years] | 181 | |||||||||||||
UL approval | UL approval number | J004 | ||||||||||||
Pressure equipment directive | sound engineering practice | |||||||||||||
ifmefector, inc. • 1100 Atwater Drive • Malvern • PA 19355 — We reserve the right to make technical alterations without prior notice. — EN-US — PN3594-01 — 24.05.2016 — | ||||||||||||||
PN3594 | ||||||||||||||
Pressure sensor with display | ||||||||||||||
PN-010-REG14-MFRKG/US/ /V | ||||||||||||||
Mechanical data | ||||||||||||||
Weight | [g] | 281.5 | ||||||||||||
Material | stainless steel (1.4404 / 316L); PBT+PC-GF30; PBT-GF20; PC | |||||||||||||
Materials (wetted parts) | stainless steel (1.4404 / 316L); Al2O3 (ceramics); FKM | |||||||||||||
Min. pressure cycles | 100 million | |||||||||||||
Tightening torque | [Nm] | 25...35; (recommended tightening torque; Depends on lubrication, sealand pressure rating) | ||||||||||||
Process connection | threaded connection G 1/4 external thread (DIN EN ISO 1179-2); Internal threadM5 | |||||||||||||
Process connection sealing | FKM (to DIN 3869) | |||||||||||||
Restrictor element integrated | no (can be retrofitted) | |||||||||||||
Displays / operating elements | ||||||||||||||
Display unit | 3 x LED, green (bar, psi, MPa) | |||||||||||||
Display | Switching status | 1 x LED, yellow | ||||||||||||
Measured values | alphanumeric display, red/green 4-digit | |||||||||||||
Remarks | ||||||||||||||
Pack quantity | 1 pcs. | |||||||||||||
Electrical connection |