IM0010 | |||||||||
Inductive sensor | |||||||||
IME2020-FBOA | |||||||||
Outputs | |||||||||
Output function | normally open / normally closed; (selectable) | ||||||||
Max. voltage drop switching output DC | [V] | 6 | |||||||
Max. voltage drop switching output AC | [V] | 6.5 | |||||||
Minimum load current | [mA] | 5 | |||||||
Max. leakage current | [mA] | 2.5 (250 V AC) / 1.3 (110 V AC) / 0.8 (24 V DC) | |||||||
Permanent current rating of switching output AC | [mA] | 250; (350 (...50 °C)) | |||||||
Permanent current rating of switching output DC | [mA] | 100 | |||||||
Short-time current rating of switching output | [mA] | 2200; (20 ms / 0,5 Hz) | |||||||
Switching frequency AC [Hz] | 20 | ||||||||
Switching frequency DC [Hz] | 55 | ||||||||
Short-circuit proof | no | ||||||||
Overload protection | no | ||||||||
Detection zone | |||||||||
Sensing range | [mm] | 20 | |||||||
Real sensing range Sr [mm] | 20 ± 10 % | ||||||||
Operating distance [mm] | 0...16.2 | ||||||||
Accuracy / deviations | |||||||||
Correction factor | steel: 1 / stainless steel: 0.7 / brass: 0.4 / aluminium: 0.3 / copper: 0.2 | ||||||||
Hysteresis Switch point drift | [% of Sr] [% of Sr] | 1...15 -10...10 | |||||||
Operating conditions | |||||||||
Ambient temperature [°C] -25...80 Protection IP 65 | |||||||||
Tests / approvals | |||||||||
EMC | EN 60947-5-2 | ||||||||
EN 55011 | class B | ||||||||
MTTF | [years] | 604 | |||||||
UL approval | Ta | 0...40 °C | |||||||
Enclosure type | Type 1 | ||||||||
voltage supply | Unlimited Voltage | ||||||||
File number UL | E174191 | ||||||||
Mechanical data | |||||||||
Weight | [g] | 183 | |||||||
Housing | rectangular | ||||||||
Mounting | non-flush mountable | ||||||||
Dimensions [mm] | 40 x 40 x 120 | ||||||||
Materials | PPE | ||||||||
Displays / operating elements | |||||||||
Display switching status 1 x LED, yellow | |||||||||
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen — We reserve the right to make technical alterations without prior notice. — EN-GB — IM0010-00 — 06.03.2003 | |||||||||
IM0010 | |||||||||
Inductive sensor | |||||||||
IME2020-FBOA | |||||||||
Electrical connection | |||||||||
Required protection | miniature fuse to IEC60127-2 sheet 1; ≤ 2 A; fast acting | ||||||||
Remarks | |||||||||
Remarks | Recommendation: Check the safe functioning of the unit after a short circuit. | ||||||||
5 positions of the active zone possible |