I apologize for the confusion earlier. Here is the corrected information for the SIEMENS SIMATIC PLC S7-400 6ES7412-2XJ05-0AB0 CPU 412-2:
Product Name: SIEMENS SIMATIC PLC S7-400 6ES7 412-2XJ05-0AB0 CPU 412-2
Introduction:
The SIEMENS SIMATIC PLC S7-400 6ES7 412-2XJ05-0AB0 CPU 412-2 is a central processing unit (CPU) designed for the SIEMENS SIMATIC S7-400 series programmable logic controllers (PLCs). It provides high-performance control and communication capabilities for large and complex automation applications.
Origin: Germany
Product Specifications:
- Product Name: SIEMENS SIMATIC PLC S7-400 6ES7 412-2XJ05-0AB0 CPU 412-2
- CPU Type: 412-2
- Compatibility: SIEMENS SIMATIC S7-400 series
- Number of Digital Inputs: Varies depending on configuration
- Number of Digital Outputs: Varies depending on configuration
- Number of Analog Inputs: Varies depending on configuration
- Number of Analog Outputs: Varies depending on configuration
- Communication Ports: Multiple communication interfaces (e.g., Ethernet, PROFIBUS, MPI)
- Memory: Varies depending on configuration
- Operating Temperature: 0 to 60°C
- Dimensions (W x H x D): Varies depending on the module
- Weight: Varies depending on the module
Product Features:
- Central processing unit (CPU) for large and complex automation applications
- Compatible with the SIEMENS SIMATIC S7-400 series
- Supports a wide range of digital and analog inputs and outputs
- Multiple communication interfaces for seamless integration into industrial networks
- Flexible memory configuration to accommodate specific application requirements
- Robust construction and reliable performance for demanding industrial environments
- Easy programming and configuration using the STEP 7 programming software
Functionality:
- The SIMATIC PLC S7-400 6ES7 412-2XJ05-0AB0 CPU 412-2 is designed to provide high-performance control and communication capabilities for large and complex automation applications.
- It is compatible with the SIEMENS SIMATIC S7-400 series, allowing for seamless integration with other modules and components.
- The CPU supports a wide range of digital and analog inputs and outputs, providing flexibility for various automation requirements.
- Multiple communication interfaces (such as Ethernet, PROFIBUS, and MPI) enable easy connectivity to other devices and networks.
- The memory configuration can be customized to accommodate specific application requirements.
- With its robust construction and reliable performance, the CPU is suitable for demanding industrial environments.
- Programming and configuration can be done using the STEP 7 programming software, which offers a user-friendly interface for efficient development and maintenance.
Please note that for more detailed technical specifications and information, it is recommended to refer to the official documentation or contact Siemens directly.
Replacement part ********* SIMATIC S7-400, CPU 412-2 Central processing unit with: work memory 512 KB, (256 KB code, 256 KB of data), 1st interface MPI/DP 12 Mbit/s, 2nd interface PROFIBUS DP |
General information | ||
Product type designation | CPU 412-2 | |
HW functional status | 03 | |
Firmware version | V5.3 | |
Product function | ||
● Isochronous mode | Yes; For PROFIBUS only | |
Engineering with | ||
● Programming package | STEP 7 V5.3 SP2 or higher with HW update | |
CiR - Configuration in RUN | ||
CiR synchronization time, basic load | 100 ms | |
CiR synchronization time, time per I/O byte | 30 µs | |
Supply voltage | ||
Rated value (DC) | Power supply via system power supply | |
Input current | ||
from backplane bus 5 V DC, typ. | 0.9 A | |
from backplane bus 5 V DC, max. | 1.1 A | |
from backplane bus 24 V DC, max. | 300 mA; 150 mA per DP interface | |
from interface 5 V DC, max. | 90 mA; At each DP interface | |
Power loss | ||
Power loss, typ. | 4.5 W | |
Power loss, max. | 5 W | |
Memory | ||
Type of memory | RAM | |
Work memory | ||
● integrated | 512 kbyte | |
● integrated (for program) | 256 kbyte | |
● integrated (for data) | 256 kbyte | |
● expandable | No | |
Load memory | ||
● expandable FEPROM | Yes; with Memory Card (FLASH) | |
● expandable FEPROM, max. | 64 Mbyte | |
● integrated RAM, max. | 512 kbyte | |
● expandable RAM | Yes; with Memory Card (RAM) | |
● expandable RAM, max. | 64 Mbyte | |
Backup | ||
● present | Yes | |
● with battery | Yes; all data | |
● without battery | No | |
Battery | ||
Backup battery | ||
● Backup current, typ. | 125 µA; up to 40 °C | |
● Backup current, max. | 550 µA | |
● Backup time, max. | See reference manual, module data, Chapter 3.3 | |
● Feeding of external backup voltage to CPU | 5 V DC to 15 V DC | |
CPU processing times | ||
for bit operations, typ. | 75 ns | |
for word operations, typ. | 75 ns | |
for fixed point arithmetic, typ. | 75 ns | |
for floating point arithmetic, typ. | 225 ns | |
CPU-blocks | ||
DB | ||
● Number, max. | 3 000; Number range: 1 to 16000 | |
● Size, max. | 64 kbyte | |
FB | ||
● Number, max. | 1 500; Number range: 0 to 7999 | |
● Size, max. | 64 kbyte | |
FC | ||
● Number, max. | 1 500; Number range: 0 to 7999 | |
● Size, max. | 64 kbyte | |
OB | ||
● Number, max. | see instruction list | |
● Size, max. | 64 kbyte | |
● Number of free cycle OBs | 1; OB 1 | |
● Number of time alarm OBs | 2; OB 10, 11 | |
● Number of delay alarm OBs | 2; OB 20, 21 | |
● Number of cyclic interrupt OBs | 2; OB 32, 35 (shortest cycle that can be set = 500 µs) | |
● Number of process alarm OBs | 2; OB 40, 41 | |
● Number of DPV1 alarm OBs | 3; OB 55-57 | |
● Number of isochronous mode OBs | 2; OB 61-62 | |
● Number of multicomputing OBs | 1; OB 60 | |
● Number of background OBs | 1; OB 90 | |
● Number of startup OBs | 3; OB 100-102 | |
● Number of asynchronous error OBs | 9; OB 80-88 | |
● Number of synchronous error OBs | 2; OB 121, 122 | |
Nesting depth | ||
● per priority class | 24 | |
● additional within an error OB | 1 | |
Counters, timers and their retentivity | ||
S7 counter | ||
● Number | 2 048 | |
Retentivity | ||
— adjustable | Yes | |
— preset | Z 0 to Z 7 | |
Counting range | ||
— lower limit | 0 | |
— upper limit | 999 | |
IEC counter | ||
● present | Yes | |
● Type | SFB | |
● Number | Unlimited (limited only by RAM capacity) | |
S7 times | ||
● Number | 2 048 | |
Retentivity | ||
— adjustable | Yes | |
— preset | No times retentive | |
Time range | ||
— lower limit | 10 ms | |
— upper limit | 9 990 s | |
IEC timer | ||
● present | Yes | |
● Type | SFB | |
● Number | Unlimited (limited only by RAM capacity) | |
Data areas and their retentivity | ||
Retentive data area (incl. timers, counters, flags), max. | Total working and load memory (with backup battery) | |
Flag | ||
● Size, max. | 4 kbyte; Size of bit memory address area | |
● Retentivity available | Yes | |
● Retentivity preset | MB 0 to MB 15 | |
● Number of clock memories | 8; in 1 memory byte | |
Local data | ||
● adjustable, max. | 8 kbyte | |
● preset | 4 kbyte | |
Address area | ||
I/O address area | ||
● Inputs | 4 kbyte | |
● Outputs | 4 kbyte | |
Process image | ||
● Inputs, adjustable | 4 kbyte | |
● Outputs, adjustable | 4 kbyte | |
● Inputs, default | 128 byte | |
● Outputs, default | 128 byte | |
● consistent data, max. | 244 byte | |
● Access to consistent data in process image | Yes | |
Subprocess images | ||
● Number of subprocess images, max. | 15 | |
Digital channels | ||
● Inputs | 32 768 | |
— of which central | 32 768 | |
● Outputs | 32 768 | |
— of which central | 32 768 | |
Analog channels | ||
● Inputs | 2 048 | |
— of which central | 2 048 | |
● Outputs | 2 048 | |
— of which central | 2 048 | |
Hardware configuration | ||
Integrated power supply | No | |
Number of expansion units, max. | 21 | |
connectable OPs | 31 | |
Multicomputing | Yes; 4 CPUs max. (with UR1 or UR2) | |
Interface modules | ||
● Number of connectable IMs (total), max. | 6 | |
● Number of connectable IM 460s, max. | 6 | |
● Number of connectable IM 463s, max. | 4; IM 463-2 | |
Number of DP masters | ||
● integrated | 2 | |
● via CP | 10; CP 443-5 Extended | |
● via IM 467 | 4 | |
● Mixed mode IM + CP permitted | No; IM 467 not suitable for use with CP 443-5 Ext. and CP 443-1 EX4x, EX20, GX20 (in PROFINET IO mode) | |
● via interface module | 0 | |
● Number of pluggable S5 modules (via adapter capsule in central device), max. | 6 | |
Number of IO Controllers | ||
● integrated | 0 | |
● via CP | 4; No mixed operation of CP443-1 EX40 and CP443-1 EX 41/EX20/GX20, max. 4 in central controller | |
Number of operable FMs and CPs (recommended) | ||
● FM | Limited by number of slots and number of connections | |
● CP, PtP | CP 440: Limited by number of slots; CP 441: Limited by number of slots and number of connections | |
● PROFIBUS and Ethernet CPs | 14; Of which 10 CPs max. or IMs as DP master, 4 PROFINET controller maximum | |
Slots | ||
● required slots | 1 | |
Time of day | ||
Clock | ||
● Hardware clock (real-time) | Yes | |
● retentive and synchronizable | Yes | |
● Resolution | 1 ms | |
● Deviation per day (buffered), max. | 1.7 s; Power off | |
● Deviation per day (unbuffered), max. | 8.6 s; For power On | |
Operating hours counter | ||
● Number | 16 | |
● Number/Number range | 0 to 15 | |
● Range of values | SFCs 2, 3 and 4: 0 to 32767 hours SFC 101: 0 to 2^31 - 1 hours | |
● Granularity | 1 h | |
● retentive | Yes | |
Clock synchronization | ||
● supported | Yes | |
● to MPI, master | Yes | |
● to MPI, slave | Yes | |
● to DP, master | Yes | |
● to DP, slave | Yes | |
● in AS, master | Yes | |
● in AS, slave | Yes | |
● on Ethernet via NTP | No; Via CP | |
Time difference in system when synchronizing via | ||
● MPI, max. | 200 ms | |
Interfaces | ||
Interfaces/bus type | 1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP | |
Number of RS 485 interfaces | 2; Combined MPI / PROFIBUS DP and PROFIBUS DP | |
Optical interface | No | |
1. Interface | ||
Interface type | MPI/PROFIBUS DP | |
Isolated | Yes | |
Interface types | ||
● RS 485 | Yes | |
● Output current of the interface, max. | 150 mA | |
Protocols | ||
● MPI | Yes | |
● PROFIBUS DP master | Yes | |
● PROFIBUS DP slave | Yes | |
MPI | ||
● Number of connections | 32; If a diagnostics repeater is used on the line, the number of connection resources on the line is reduced by 1 | |
● Transmission rate, max. | 12 Mbit/s | |
Services | ||
— PG/OP communication | Yes | |
— Routing | Yes | |
— Global data communication | Yes | |
— S7 basic communication | Yes | |
— S7 communication | Yes | |
— S7 communication, as client | Yes | |
— S7 communication, as server | Yes | |
PROFIBUS DP master | ||
● Number of connections, max. | 16; If a diagnostics repeater is used on the line, the number of connection resources on the line is reduced by 1 | |
● Transmission rate, max. | 12 Mbit/s | |
● Number of DP slaves, max. | 32 | |
Services | ||
— PG/OP communication | Yes | |
— Routing | Yes; S7 routing | |
— Global data communication | No | |
— S7 basic communication | Yes | |
— S7 communication | Yes | |
— S7 communication, as client | Yes | |
— S7 communication, as server | Yes | |
— Equidistance | Yes | |
— Isochronous mode | Yes | |
— SYNC/FREEZE | Yes | |
— Activation/deactivation of DP slaves | Yes | |
— Direct data exchange (slave-to-slave communication) | Yes | |
— DPV1 | Yes | |
Address area | ||
— Inputs, max. | 2 kbyte | |
— Outputs, max. | 2 kbyte | |
User data per DP slave | ||
— User data per DP slave, max. | 244 byte | |
— Inputs, max. | 244 byte | |
— Outputs, max. | 244 byte | |
— Slots, max. | 244 | |
— per slot, max. | 128 byte | |
PROFIBUS DP slave | ||
● Number of connections | 16 | |
● GSD file | http://support.automation.siemens.com/WW/view/en/113652 | |
● Transmission rate, max. | 12 Mbit/s | |
● automatic baud rate search | No | |
● Address area, max. | 32; Virtual slots | |
● User data per address area, max. | 32 byte | |
— of which consistent, max. | 32 byte | |
Services | ||
— PG/OP communication | Yes; with interface active | |
— Routing | Yes; with interface active | |
— Global data communication | No | |
— S7 basic communication | No | |
— S7 communication | Yes | |
— S7 communication, as client | Yes | |
— S7 communication, as server | Yes | |
— Direct data exchange (slave-to-slave communication) | No | |
— DPV1 | No | |
Transfer memory | ||
— Inputs | 244 byte | |
— Outputs | 244 byte | |
2. Interface | ||
Interface type | PROFIBUS DP | |
Isolated | Yes | |
Interface types | ||
● RS 485 | Yes | |
● Output current of the interface, max. | 150 mA | |
Protocols | ||
● PROFIBUS DP master | Yes | |
● PROFIBUS DP slave | Yes | |
PROFIBUS DP master | ||
● Number of connections, max. | 16 | |
● Transmission rate, max. | 12 Mbit/s | |
● Number of DP slaves, max. | 64 | |
Services | ||
— PG/OP communication | Yes | |
— Routing | Yes; S7 routing | |
— Global data communication | No | |
— S7 basic communication | Yes | |
— S7 communication | Yes | |
— S7 communication, as client | Yes | |
— S7 communication, as server | Yes | |
— Equidistance | Yes | |
— Isochronous mode | Yes | |
— SYNC/FREEZE | Yes | |
— Activation/deactivation of DP slaves | Yes | |
— Direct data exchange (slave-to-slave communication) | Yes | |
— DPV1 | Yes | |
Address area | ||
— Inputs, max. | 4 kbyte | |
— Outputs, max. | 4 kbyte | |
User data per DP slave | ||
— User data per DP slave, max. | 244 byte | |
— Inputs, max. | 244 byte | |
— Outputs, max. | 244 byte | |
— Slots, max. | 244 | |
— per slot, max. | 128 byte | |
PROFIBUS DP slave | ||
● Number of connections | 16 | |
● GSD file | http://support.automation.siemens.com/WW/view/en/113652 | |
● Transmission rate, max. | 12 Mbit/s | |
● Address area, max. | 32 | |
● User data per address area, max. | 32 byte | |
— of which consistent, max. | 32 byte | |
Services | ||
— Routing | Yes | |
Transfer memory | ||
— Inputs | 244 byte | |
— Outputs | 244 byte | |
Protocols | ||
SIMATIC communication | ||
● S7 routing | Yes | |
Open IE communication | ||
● ISO-on-TCP (RFC1006) | Via CP 443-1 and loadable FB | |
— Data length, max. | 1 452 bytes via CP 443-1 Adv. | |
Web server | ||
● supported | No | |
Isochronous mode | ||
Equidistance | Yes | |
Number of DP masters with isochronous mode | 2 | |
User data per isochronous slave, max. | 244 byte | |
shortest clock pulse | 1.5 ms; 0.5 ms without use of SFC 126, 127 | |
max. cycle | 32 ms | |
communication functions / header | ||
PG/OP communication | Yes | |
● Number of connectable OPs without message processing | 31 | |
● Number of connectable OPs with message processing | 31; When using Alarm_S/SQ and Alarm_D/DQ | |
Data record routing | Yes | |
Global data communication | ||
● supported | Yes | |
● Number of GD loops, max. | 8 | |
● Number of GD packets, transmitter, max. | 8 | |
● Number of GD packets, receiver, max. | 16 | |
● Size of GD packets, max. | 54 byte | |
● Size of GD packet (of which consistent), max. | 1 variable | |
S7 basic communication | ||
● communication function / S7 basic communication | Yes | |
● User data per job, max. | 76 byte | |
● User data per job (of which consistent), max. | 1 variable | |
S7 communication | ||
● supported | Yes | |
● as server | Yes | |
● as client | Yes | |
● User data per job, max. | 64 kbyte | |
● User data per job (of which consistent), max. | 462 byte; 1 variable | |
S5 compatible communication | ||
● supported | Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5 | |
● User data per job, max. | 8 kbyte | |
● User data per job (of which consistent), max. | 240 byte | |
● Number of simultaneous AG-SEND/AG-RECV orders per CPU, max. | 24/24 | |
Standard communication (FMS) | ||
● supported | Yes; Via CP and loadable FB | |
Number of connections | ||
● overall | 32 | |
● usable for PG communication | 31 | |
— reserved for PG communication | 1 | |
— adjustable for PG communication, max. | 0 | |
● usable for OP communication | 31 | |
— reserved for OP communication | 1 | |
— adjustable for OP communication, max. | 0 | |
● usable for S7 basic communication | 30 | |
— reserved for S7 basic communication | 0 | |
— adjustable for S7 basic communication, max. | 0 | |
● usable for S7 communication | 30 | |
— reserved for S7 communication | 0 | |
— adjustable for S7 communication, max. | 0 | |
● usable for routing | 15 | |
— reserved for routing | 0 | |
— adjustable for routing, max. | 0 | |
S7 message functions | ||
Number of login stations for message functions, max. | 31; Max. 31 with Alarm_S/SQ and Alarm_D/DQ (OPs); max. 8 with Alarm_8 and Alarm_P (e.g. WinCC) | |
Symbol-related messages | Yes | |
SCAN procedure | Yes | |
Program alarms | Yes | |
Process diagnostic messages | Yes | |
simultaneously active Alarm-S blocks, max. | 250; Simultaneously active alarm_S/SQ blocks or alarm_D/DQ blocks | |
Alarm 8-blocks | Yes | |
● Number of instances for alarm 8 and S7 communication blocks, max. | 300 | |
● preset, max. | 150 | |
Process control messages | Yes | |
Number of archives that can log on simultaneously (SFB 37 AR_SEND) | 4 | |
Number of messages | ||
● overall, max. | 256 | |
● in 100 ms grid, max. | 0 | |
● in 500 ms grid, max. | 256 | |
● in 1000 ms grid, max. | 256 | |
Number of additional values | ||
● with 100 ms grid, max. | 0 | |
● with 500, 1000 ms grid, max. | 1 | |
Test commissioning functions | ||
Status block | Yes; Up to 2 simultaneously | |
Single step | Yes | |
Number of breakpoints | 4 | |
Status/control | ||
● Status/control variable | Yes; Up to 16 variable tables | |
● Variables | Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters | |
● Number of variables, max. | 70; Status/control | |
Forcing | ||
● Forcing | Yes | |
● Forcing, variables | Inputs, outputs, bit memories, peripheral inputs, peripheral outputs | |
● Number of variables, max. | 64 | |
Diagnostic buffer | ||
● present | Yes | |
● Number of entries, max. | 400 | |
— adjustable | Yes | |
— preset | 120 | |
Service data | ||
● can be read out | Yes | |
Standards, approvals, certificates | ||
CE mark | Yes | |
CSA approval | Yes | |
UL approval | Yes | |
cULus | Yes | |
FM approval | Yes | |
RCM (formerly C-TICK) | Yes | |
KC approval | Yes | |
EAC (formerly Gost-R) | Yes | |
Use in hazardous areas | ||
● ATEX | ATEX II 3G Ex nA IIC T4 Gc | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | 0 °C | |
● max. | 60 °C | |
configuration / header | ||
Configuration software | ||
● STEP 7 | Yes | |
configuration / programming / header | ||
● Command set | see instruction list | |
● Nesting levels | 7 | |
● Access to consistent data in process image | Yes | |
● System functions (SFC) | see instruction list | |
● System function blocks (SFB) | see instruction list | |
Programming language | ||
— LAD | Yes | |
— FBD | Yes | |
— STL | Yes | |
— SCL | Yes | |
— CFC | Yes | |
— GRAPH | Yes | |
— HiGraph® | Yes | |
configuration / programming / number of simultaneously active SFC / header | ||
— DPSYC_FR | 2; SFC 11; per interface | |
— D_ACT_DP | 8; SFC 12; per interface | |
— RD_REC | 8; SFC 59; per interface | |
— WR_REC | 8; SFC 58; per interface | |
— WR_PARM | 8; SFC 55; per interface | |
— PARM_MOD | 1; SFC 57; per interface | |
— WR_DPARM | 2; SFC 56; per interface | |
— DPNRM_DG | 8; SFC 13; per interface | |
— RDSYSST | 8 | |
— DP_TOPOL | 1; SFC 103; per interface | |
configuration / programming / number of simultaneously active SFB / header | ||
— RDREC | 8; SFB 52; per interface, but not more than 32 across all external interfaces | |
— WRREC | 8; SFB 53; per interface, but not more than 32 across all external interfaces | |
Know-how protection | ||
● User program protection/password protection | Yes | |
Dimensions | ||
Width | 25 mm | |
Height | 290 mm | |
Depth | 219 mm | |
Weights | ||
Weight, approx. | 700 g |