Product Description | |
SITOP DC UPS MODULE 15A WITHOUT INTERF. SITOP DC UPS MODULE 24 V/15 A UNINTERRUPTIBLE POWER SUPPLY WITHOUT INTERFACE INPUT: 24 V DC/16 A OUTPUT: 24 V DC/15 A | |
Input | |
Supply voltage for DC Rated value | 24 V |
Voltage curve at input | DC |
input voltage range | 22 ... 29 V DC |
Mains buffering | |
Type of energy storage | with batteries |
Charging current | |
● 1 | 0.35 A |
● 2 | 0.7 A |
Output | |
Output voltage | |
● in normal operation for DC Rated value | 24 V |
● in buffering mode for DC Rated value | 24 V |
Formula for output voltage | Vin - approx. 0.5 V |
ON-delay time typical | 1 s |
Voltage increase time of the output voltage typical | 60 ms |
Output current Rated value | 15 A |
Property of the output Short-circuit proof | Yes |
Active power supplied typical | 360 W |
Efficiency | |
Efficiency in percent | |
● at rated output current at rated output current typical | 96.20% |
● in case of accumulator operation typical | 96% |
Active power loss | |
● at rated output current at rated output current typical | 14 W |
● in case of accumulator operation typical | 15 W |
Protection and monitoring | |
Product function | |
● reverse polarity protection against energy storage unit polarity reversal | Yes |
● reverse polarity protection against input voltage polarity reversal | Yes |
Signaling | |
Display version | |
● for normal operation | Normal operation: LED green (OK), floating changeover contact "Bat/OK" to setting "OK" ("OK" means: Voltage of the supplying power supply unit is greater than cut-in threshold set at the DC UPS module); Lack of buffer standby: LED red (alarm), floating changeover contact "Alarm/Bat" to setting "Alarm"; Battery replacement required: LED red (alarm) flashing with approx. 0.25 Hz, floating changeover contact "Alarm/Bat" switching with approx. 0.25 Hz; Energy storage > 85%: LED green (Bat > 85%), floating NO contact "Bat > 85" closed; Permissible contact current capacity: DC 60 V/1 A or AC 30 V /1 A |
● in buffering mode | Buffered mode: LED yellow (Bat), floating changeover contact "OK/Bat" to setting "Bat"; Prewarning battery voltage < 20.4 VDC: LED red (alarm), floating changeover contact "Alarm/Bat" to setting "Alarm"; Energy storage > 85%: LED green (Bat > 85%), floating NO contact "Bat > 85" closed |