Product Description:
SIMATIC DP, Electronics module ET 200S 4AI standard I-2-wire, 4-20 mA; 13 bit, 15 mm width, for 2-wire transducer Cycle time 40
ms/module with SF LED (group fault)
Establish reliable communication links between your PLC and peripheral devices with this I/O module from Siemens. It's designed for use with controllers in the SIMATIC ET 200S series and it lets you control and monitor components that have analogue inputs. Thanks to four integrated input ports, you can connect multiple devices such as sensors and automate their functions. The I/O module's thermoplastic housing offers impact and abrasion resistance, making it suitable for use in harsh industrial environments. It also has air vents to support passive cooling from the atmosphere, preventing the build-up of heat and optimising performance. Modules like this are commonly used in robotics and industrial automation systems.
• Voltage rating of 24V DC for use in low-voltage systems
• Compact dimensions of 81 (height) x 15 (width) x 52mm (depth) for installation in setups with limited space
• Low power loss of 0.6W for effective energy use
Supply voltage | |
Load voltage L+ | |
● Rated value (DC) | 24 V; From power module |
● Reverse polarity protection | Yes |
Input current | |
from load voltage L+ (without load), max. | 125 mA |
from backplane bus 3.3 V DC, max. | 10 mA |
Output voltage | |
Power supply to the transmitters | |
● present | Yes |
Power loss | |
Power loss, typ. | 0.6 W |
Address area | |
Address space per module | |
● Address space per module, max. 8 byte | 8 byte |
Analog inputs | |
Number of analog inputs | 4 |
permissible input current for current input (destruction limit), max. | 30 mA; limited electronically |
Cycle time (all channels) max. | 40 ms; 33 to 40 ms |
Input ranges (rated values), currents | |
● 4 mA to 20 mA | Yes; Into 25 Ohm |
Cable length | |
● shielded, max. | 200 m |
Analog value generation for the inputs | |
Integration and conversion time/resolution per channel | |
● Resolution with overrange (bit including sign),max. | 13 bit; 4 to 20 mA: 13 bit |
● Integration time, parameterizable | Yes |
● Integration time (ms) | 16,67 / 20 ms |
● Interference voltage suppression for interference frequency f1 in Hz | 50 / 60 Hz |
Errors/accuracies | |
Operational error limit in overall temperature range | |
● Current, relative to input range, (+/-) | 0.40% |
Basic error limit (operational limit at 25 °C) | |
● Current, relative to input range, (+/-) | 0.30% |
Interrupts/diagnostics/status information | |
Diagnostic messages | |
● Wire-break | Yes; Measuring range 1 to 5 V only |
● Group error | Yes |
● Overflow/underflow | Yes |
Diagnostics indication LED | |
● Group error SF (red) | Yes |
Parameter | |
Remark | 7 byte |
Diagnostics wire break | 1 |
Measurement type/range | 1 |
Group diagnostics | 1 |
Overflow/underflow | 1 |
Potential separation | |
Potential separation analog inputs | |
● between the channels | No |
● between the channels and backplane bus | Yes |
● Between the channels and load voltage L+ | No |
Isolation | |
Isolation tested with | 500 V DC |
Dimensions | |
Width | 15 mm |
Height | 81 mm |
Depth | 52 mm |
Weights | |
Weight, approx. | 40 g |