Fixed Industrial Toxic And Flammable Gas Leak Detector 4-20ma Output
Product Description
The K800 Series Fixed Gas Detector provides comprehensive monitoring of combustible, toxic gas hazards in potentially explosive atmospheres, indoors and outdoors-and is marked by installation ease and flexibility, user-friendly operation and cost-effective gas monitoring.
Application
The detector working with gas controller are widely used to detect gas in refinery, chemical plant, LPG station, boiler room, painting plant and other places with gas exists, effectively protect personnel and plant from flammable, toxic and oxygen hazards.
Key Features
1) Digital and analog outputs
2) LED light status indicator for alarm conditions
3) The relay can trigger alarms or process controls
4) Three models available measure toxic gases, VOCs, or combustibles
5) Explosion-proof enclosure
6) CERTIFICATIONS:UL, CE, CMC, Ex, MA (SAFETY CERTIFICATE OF APPROVAL FOR COAL MINING PRODUCTS IN CHINA
Item: | K800 Fixed gas detector |
Sensor Cell: | UK sensors (brand CITY, Alphasense, Dynament etc.), US (brand Honeywell), Japan and Germany sensors |
Lifetime of Detector: | 2 - 5 years |
Sample Mode | Diffusion |
Output Signals: | 4-20mA&RS485 |
Operating Voltage: | 24V DC |
Response Time | T90≤30S |
Suitable Cable | RVVP3*1.5mm2 cable |
Wiring | 3-wire/4-wire |
Relay Output | 1 relay output |
Operation Method | with remote control |
Ingress Protection | IP66 |
Body Material | YL113 aluminum +304L S/S |
Display | 4 digital LED readout display (LCD display with power, fault,alarm-1,alarm-2 indicator light) |
Transmission Cable | Three core shield cable, 3×1.5mm |
Ambient Temperature: | - 20 ° C ~ + 50 ° C |
Relative Humidity: | 10~90%RH(non condensation) |
Working Pressure: | 86~106Kpa |
Detection Precision: | ±5%FS |
Net Weight: | K800-N: 1.6kg K800-DA:2 kg |
Dimension(mm): | 183×143×107mm |
Certificates | EN 61326-1:2013; EX (Exd IICT6 Gb;Ex tD A21IP66T80°C); SIL(SIL2); UL 508 UL1203 |
Explosion-proof Grade: | Exd II CT6 |
Protection Grade: | IP65 |
Common Used Gas Detection List
No. | Detection gas | Range | Accuracy | 90% response time | Min readout | Low/high alarm |
1 | PH3 | 0-5ppm | ±5%(F.S) | ≤25s | 0.01ppm | 0.3ppm/5ppm |
2 | O2 | 0-30%vol | ±5%(F.S) | ≤15s | 0.1%vol | 18%vol/23%vol |
3 | EX(LEL/CH4) | 0-100%lel | ±5%(F.S) | ≤15s | 1%lel | 25%lel/50%lel |
4 | CO | 0-2000 ppm | ±5%(F.S) | ≤25s | 1 ppm | 50ppm/100ppm |
5 | H2S | 0-100 ppm | ±5%(F.S) | ≤30s | 1 ppm | 10ppm/20ppm |
6 | NO2 | 0-20 ppm | ±5%(F.S | ≤25s | 0.1 ppm | 3ppm/10ppm |
7 | NO | 0-250 ppm | ±5%(F.S) | ≤60s | 1 ppm | 25ppm/50 ppm |
8 | SO2 | 0-100 ppm | ±5%(F.S) | ≤30s | 0.1 ppm | 2 ppm /10 ppm |
9 | CL2 | 0-20 ppm | ±5%(F.S) | ≤30s | 0.1 ppm | 1 ppm /10 ppm |
10 | NH3 | 0-200ppm | ±5%(F.S) | ≤50s | 1 ppm | 25 ppm /50 ppm |
11 | H2 | 0-1000 ppm | ±5%(F.S) | ≤60s | 1 ppm | 50 ppm /100 ppm |
12 | HCN | 0-50ppm | ±5%(F.S) | ≤200s | 0.1ppm | 10ppm/20ppm |
13 | HCL | 0-20ppm | ±5%(F.S) | ≤60s | 0.1ppm | 5ppm/10ppm |
14 | CH4(IR) | 0-5%vol | ±5%(F.S) | ≤60s | 0.01%vol | customized |
15 | CO2(IR) | 0-5%vol (0-5000ppm) | ±5%(F.S) | ≤60s | 0.1%vol (1ppm) | customized |
16 | PID(VOCs) | 1-1999ppm | ±5%(F.S) | ≤20 | 0.1ppm | customized |
17 | C3H8 | 0-5%vol | ±5%(F.S) | ≤60s | 0.01%vol | customized |
18 | O3 | 0-10ppm | ±5%(F.S) | ≤30s | 0.02ppm | 1ppm/2ppm |