Customized design Pole Mount Cabinet with Battery PDU and power distribution
Quick Details:
Pole Mount Outdoor Telecom Cabinet Technical Parameters:
Model | DAXIN-7058350 |
Product Name | Outdoor Telecom Cabinet |
Manufacturer | Shenzhen Daxin |
Cabinet Dimension | W700mm*D580mm*H350mm |
IP Level | IP54/IP55/IP65 |
Material | 1.5mm galvanized steel, single wall |
Mounting Way | Pole mount |
Cabinet Lock | Round Lock |
Access | Door sensor |
Battery Shelf | Two shelves |
Fan | 1 fans on the top |
Color | RAL7035 |
Surface finish | Outdoor Powder Coating |
Orther accessory | Battery |
UPS | |
PDU | |
Fan |
Cabinet Environmental Parameter
Environmental parameters | Environmental conditions for use | Transportation environmental conditions | Storage environmental conditions | conform to | notes | |||
type | parameter | unit | Relevant standards | |||||
Weather | external temperature | low temperature | ℃ | -40 | -40 | -25 | YD/T1058-2000中 | "-40℃ Can start at full load, |
high temperature | ℃ | 45 | 70 | 55 | 4.1.1and4.1.2 | "+55~+65℃Linear derating20%. | ||
temperature variation | ℃/min | / | 1 | / | ETS300019-2-2T2.3 | |||
humidity | relative humidity | % | 5-90 | 90(40±2℃) | / | YD/T1058-2000中4.1.3 | Short term testing requirements: 0-95%, maximum value of 95%, non condensing | |
air pressure | low pressure | Kpa | 86 | 70 | 70 | YD/T1058-2000中4.1.4 | Only apply to modules | |
high atmospheric pressure | Kpa | 106 | 106 | 106 | ||||
altitude | m | ≤4000 | When the altitude exceeds 2000m, for every 100m increase, the temperature decreases by 0.5 ℃ |
Electrical characteristics
1 Input characteristics | |||||
Serial Number | project | technical requirement | unit | notes | |
1.1 | Input Voltage | 90—300 | Vac | 176-300Vac full load output, 90-175Vac reduced load output | |
1.2 | Input maximum current | 57 | A | ||
1.3 | Input Rated Voltage | 220 | Vac | Phase voltage | |
1.4 | Input voltage frequency | 47—63(The typical value is50/60) | Hz | ||
1.5 | Input power factor | ≥0.99 | Full load working state | ||
2 output characteristic | |||||
Serial Number | project | technical requirement | Unit | notes | |
2.1 | Output rated voltage | -54 | Vdc | IN220Vac | |
2.2 | Output voltage range | -42— -58 | Vdc | Adjustable through monitoring (test condition: no load) | |
2.3 | Output rated current | 150 | A | ||
2.4 | Output Rating Power | 8.7 | KW | ||
2.5 | Output ripple and noise | ≤200 | mVp-p | The oscilloscope bandwidth should be20MHz, | |
Probe parallel with 10u+104 capacitor | |||||
2.6 | Startup output delay | 3—8 | S | IN 220Vac, | |
2.7 | Voltage stabilization accuracy | ≤±1% | |||
2.8 | Noise index | Broadband clutter | ≤100 | mV | 3.4—150 KHz |
Sound voltage | ≤30 | mV | 150—30 MHz | ||
Telephone balance weight | ≤2 | mV | |||
noise voltage | |||||
2.9 | dynamics | overshoot amplitude | △V:≤5 | %Vo | 25%—50%—25% |
in response to | recovery time | △t:≤500 | µS | 50%—75%—50%load change | |
2.1 | Unequal current distribution | ≤5% | Module parallel 50% -100% rated output | ||
(Functional modules can work in parallel) | |||||
2.11 | temperature coefficient | ±0.02 | %/℃ | ||
2.12 | output efficiency | ≥95% | 220Vac/Rated load (typical value), high-efficiency module | ||
≥92% | 220Vac/Rated load (typical value), universal module | ||||
≥87% | 110VAC/rated load |
About product real pictures: