1. Description
KYN28A-12 is the switchgear apply in the single busbar power system and single busbar sectionalized power system with three-phase AC 50Hz,7.2~12kV.It can be used for receiving & distributing electric power of the transmission and distribution control.
2. Working Condition
Indoor ambient temperature:
Max. temperature: +40℃
Daily average temperature: +35℃
Min. temperature: -15℃
Indoor ambient humidity:
Daily average relative humidity: ≤95%
Monthly average relative humidity: ≤90%
Altitude for place of installation : ≤1000m
Earthquake intensity: ≤magnitude 8
Applicable in the places without fire, explosive risk, serious polluted and chemical corrosive.
(Exceeding above working condition is available as customized product)
Rated voltage | kV | 12 | |
Rated insulated level | 1min Power frequency withstand voltage (available value) | kV | 42 |
Lighting impulse withstand voltage(peak value) | kV | 75 | |
Rated frequency | Hz | 50 | |
Rated current of main busbar | A | 630,1250,1600,2000,2500,3150,4000﹡ | |
Rated current of branch busbar | A | 630,1250,1600,2000,2500,3150,4000 | |
4s Thermal stability current (available value) | kA | 16,20,25,31.5,40﹡﹡ | |
Rated dynamic stability current(peak value) ﹡﹡﹡ | kA | 40,50,63,80,100 |
Remark:
﹡t needs to be equipped with ventilation device.
﹡﹡At the rate of 40kA is 3 seconds.
﹡﹡﹡The short-circuit capacity of instrument transformer needs to be considered separately.
4. Standard
---- IEC62271-200:2003
---- GB3906-2006
---- GB/T11022-1999
---- DL/T 404-2007