1. CKVB-12/GB is fixed/withdrawable circuit breaker.
2. Working Condition
2.1 Ambient air temperature: -25℃~+40℃
2.2 Ambient humidity:
---- relative average daily humidity: ≤95%
---- relative average daily water vapor pressure: ≤2.2kPa
---- relative average monthly humidity: ≤90%
---- relative average monthly water vapor pressure: ≤1.8kPa
2.3 Altitude: ≤1000m
2.4 Earthquake intensity: ≤magnitude 8
2.5 Ambient air doesn’t obviously pollute by dust, smoke, corrosive or combustible gas, vapors or salt spray.
(Exceeding above working condition is available as customized product)
3. Technical Data
Description | Unit | Parameter | ||||||||||||||||
Rated voltage | kV | 12 | ||||||||||||||||
Short-time withstand voltage | kV | 42 | ||||||||||||||||
Lighting impulse withstand voltage | kV | 75 | ||||||||||||||||
Rated frequency | Hz | 50 | ||||||||||||||||
Rated current | A | 630 | 1250 | 1600 | 2000,2500 | 3150,4000 | ||||||||||||
Pole centre distance | mm | 150 | 210 | 150 | 210 | 275 | 210 | 275 | 275 | 275 | ||||||||
Rated short-circuit breaking current | kA | 25 | 31.5 | 25 | 31.5 | 25 | 31.5 | 25 | 31.5 | 40 | 40 | 31.5 | 40 | 31.5 | 40 | 31.5 | 40 | 40 |
Rated short-circuit making current | kA | 63 | 80 | 63 | 80 | 63 | 80 | 63 | 80 | 100 | 100 | 80 | 100 | 80 | 100 | 80 | 100 | 100 |
Short-time withstand current(4s) | kA | 25 | 31.5 | 25 | 31.5 | 25 | 31.5 | 25 | 31.5 | 40 | 40 | 31.5 | 40 | 31.5 | 40 | 31.5 | 40 | 40 |
Rated peak withstand current | kA | 63 | 80 | 63 | 80 | 63 | 80 | 63 | 80 | 100 | 100 | 80 | 100 | 80 | 100 | 80 | 100 | 100 |
Operating sequence | Opening-0.3s –closing opening-180s –closing opening | |||||||||||||||||
Opening time | ms | 20~50 | ||||||||||||||||
Arc time | ms | ≤15 | ||||||||||||||||
Closing time | ms | 30~70 | ||||||||||||||||
Average closing speed | m/s | 0.5~0.8 | ||||||||||||||||
Average opening speed | m/s | 0.9~1.2 | ||||||||||||||||
Bounce time for contact’s closing | ms | ≤2 | ||||||||||||||||
Asynchronous time for contact’s closing / opening | ms | ≤2 | ||||||||||||||||
Allowable accumulated wearing thickness of moving/fixing contact | mm | 3 |
4. Standard
---- GB1984-2003
---- IEC60056-2001
---- GB/T16927-1997
---- GB/T 4473-2008
---- DL/T403-2000
---- JB/T3855-2008