Reduce Energy Costs and Carbon Emissions with CNM Series Modular UPS
Product Description
The CNM series rack-mounted modular UPS is a high-performance, scalable, and reliable power protection solution for mission-critical applications. It offers a wide range of power ratings, from 1kVA to 10kVA, to meet the diverse requirements of data centers, telecommunications networks, industrial facilities, and other critical infrastructure. The CNM series UPS is designed with a modular architecture that allows for easy scalability and redundancy. The hot-swappable power modules and batteries enable quick and easy maintenance without interrupting critical operations. | ![]() |
Product Feature
![]() |
|
Product Advantages
Protect your critical applications from power outages and disturbances.
N+1 redundancy ensures continuous operation even in the event of a power module failure.
Monitor and control your UPS system remotely for enhanced visibility and control.
Identify and troubleshoot potential issues before they cause downtime.
| ![]() |
Data Sheet
Model CNM | 100/25 | 120/30 | 150/25 | 180/30 |
Rate Power | 100KVA/100KW | 120VA/120KW | 150VA/150KW | 180KVA/180KW |
Main input | ||||
input | 3P5W(3P+N+PE) | |||
Rate Voltage | 380/400/415VAC(L-L);220/230/240VAC(L-N) | |||
Rate Freq | 50/60Hz | |||
input PF | >0.99 | |||
Current Distortion | THDi<3%(100%Linear load) | |||
Voltage Range | 304-478VAC(L-L)full load;304-228VAC(L-L)power derate from 100%to 75% | |||
Freg.Range | 40-70Hz | |||
Battery | ||||
Rate voltage | ±240VDC | |||
Charging Capacity | 20%*Pout | |||
Charging Accuracy | ±1% | |||
Bypass | ||||
Rate Voltage | 380/400/415VAC(L-L);220/230/240VAC(L-N) | |||
Voltage Range | Range:-40%-+25%,Settable,default-20%~+15% | |||
Overload | 110%,long time operation;110%<load<125%,5 mins 125%<load<150%,1min;>150%,1second | |||
Inverter | ||||
Rate Voltage | 380/400/415VAC(L-L);220/230/240VAC(L-N) | |||
Rate Freq | 50/60Hz | |||
Output PF | 1 | |||
Voltage Accuracy | ±1.0% | |||
Load Response | <5%(20%-80%-20%step load) | |||
Recovery Time | <20ms(0%-100%-0%stepload) | |||
Output THDu | <1%(linear load),<5%(non-linear load according to IEC 62040-3) | |||
Overload | 110%,1 hour;125%,10 mins;150%,1 min;>150%,200ms | |||
Frequency Accuracy | 0.1% | |||
Synchronize Window | Settable,+0.5Hz-±5Hz,default+3Hz | |||
5lew Rate | Settable,0.5Hz/5-3Hz/5,default 0.5Hz/S | |||
Crest Factor | 3:1 | |||
Phase Accuracy | 120⁰ ±0.5° | |||
System | ||||
Efficiency | Normal Mode296%;Battery Mode296% | |||
Display | LED+7 inch touch LCD | |||
Certification-Safety | EC62040-1,IEC60950-1 | |||
Certification-EMS | EC62040-2;IEC61000-4-2(ESD);IEC61000-4-3(RS);IEC61000-4-4(EFT);IEC61000-4-5(Surge) | |||
P Degree | IP20 | |||
Configuration | USB,RS232,RS485,Dry contact,Cold start | |||
0ption | SNMP card,A5400 card,Parallel kit,LBS,Airfilter,Bottom entry kit,Wheels kit | |||
Environment | 0-40°℃(operation);-25~70(storage);0-95%(Humidity,non-condensing) | |||
Noise(dB)(1meter) | 65dB@100%load,62dB @45%load | |||
Dimentio | ||||
Cabinet(W*D*H)mm | 482*816*796(18U,wheels not included | 482*816*1018(23U,wheels not included | ||
Module(W*D*H)mm | 440*678*85(2U) |
Applications
| ![]() |
Packing&Shipping
Factory View